Adding FLN Application Libraries

During the integration, you are asked to select FLN application libraries. Since there are hundreds of FLN applications, select only those needed for your project. Otherwise, you will hinder system performance. Also, there are FLN libraries for both EN (US Standard) and SI (Metric) environments. Install only those needed for your environment. In other words, install one group or the other, but not both.

The project template BA_NA includes an FLN Application Guide that shows which libraries must be imported for the various TEC application numbers. You can find the guide in the Desigo CC System Browser. Once you have selected Application View and Show Description, select:

Applications > Documents > FLN Application Library Guide

Alternatively, you can click the link at the end of this topic to view the full list of supported applications.

The following table shows a list of library categories, followed by their names in the Import Libraries dialog box.

Library Category

EN

SI

APOGEE_CUSTOM

BA_Room_TEC_APOGEE_CUSTOM_EN_HQ_1.gms

BA_Room_TEC_APOGEE_CUSTOM_SI_HQ_1.gms

APOGEE_LABS

BA_Room_TEC_APOGEE_LABS_EN_HQ_1.gms

BA_Room_TEC_APOGEE_LABS_SI_HQ_1.gms

APOGEE_P1

BA_Room_TEC_APOGEE_P1_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P1_AI_HQ_1.gms

APOGEE_P1SEC

BA_Room_TEC_APOGEE_P1SEC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P1SEC_SI_HQ_1.gms

APOGEE_ATEC

BA_Room_TEC_APOGEE_ATEC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_ATEC_SI_HQ_1.gms

APOGEE_BTEC

BA_Room_TEC_APOGEE_BTEC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_BTEC_SI_HQ_1.gms

APOGEE_PTEC

BA_Room_TEC_APOGEE_PTEC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_PTEC_SI_HQ_1.gms

APOGEE_INT

BA_Room_TEC_APOGEE_INT_EN_HQ_1.gms

BA_Room_TEC_APOGEE_INT_SI_HQ_1.gms

APOGEE_LON

BA_Room_TEC_APOGEE_LON_EN_HQ_1.gms

BA_Room_TEC_APOGEE_LON_SI_HQ_1.gms

APOGEE_MISC

BA_Room_TEC_APOGEE_MISC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_MISC_SI_HQ_1.gms

APOGEE_P2_PTEC

BA_Room_TEC_APOGEE_P2_PTEC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_PTEC_SI_HQ_1.gms

APOGEE_P2_P1SEC

BA_Room_TEC_APOGEE_P2_P1SEC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_P1SEC_SI_HQ_1.gms

APOGEE_P2_P1

BA_Room_TEC_APOGEE_P2__P2_P1_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_ P2_P1_SI_HQ_1.gms

APOGEE_P2_MISC

BA_Room_TEC_APOGEE_P2__MISC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_ MISC_SI_HQ_1.gms

APOGEE_P2_LON

BA_Room_TEC_APOGEE_P2__LON_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_ LON_SI_HQ_1.gms

APOGEE_P2_LABS

BA_Room_TEC_APOGEE_P2__LABS_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_ LABS_SI_HQ_1.gms

APOGEE_P2_INT1

BA_Room_TEC_APOGEE_P2__INT1_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_ INT1_SI_HQ_1.gms

APOGEE_P2_Custom

BA_Room_TEC_APOGEE_P2__Custom_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_ Custom_SI_HQ_1.gms

APOGEE_P2_BTEC

BA_Room_TEC_APOGEE_P2__BTEC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_ BTEC_SI_HQ_1.gms

APOGEE_P2_ATEC

BA_Room_TEC_APOGEE_P2__ATEC_EN_HQ_1.gms

BA_Room_TEC_APOGEE_P2_ ATEC_SI_HQ_1.gms

 

FLN Application Library Master List

Use the following table to match your FLN applications to the appropriate TEC library, and then install only the libraries you need for your project. Recent additions are indicated with a NEW next to them.

Appl

Description

Library

600

Fume Hood - 9 Horizontal combination Sash with VSD

APOGEE_LABS

603

Fume Hood - Single or Multi-vertical Sash with Damper

APOGEE_LABS

604

Fume Hood - 603 with VSD output

APOGEE_CUSTOM

605

Fume Hood - Horizontal Sash with Damper

APOGEE_LABS

606

Fume Hood - 605 with VSD output

APOGEE_CUSTOM

607

Fume Hood - Combination Sash with Damper

APOGEE_LABS

608

Fume Hood - 607 with VSD output

APOGEE_CUSTOM

613

Fume Hood - 4 Vertical across

APOGEE_CUSTOM

615

Fume Hood - 5 to 9 Horizontal Sash with Damper

APOGEE_CUSTOM

617

Fume Hood - 9 Horizontal Combination Sash with Damper

APOGEE_CUSTOM

625

Fume Hood - Cal. Hood, 4 Horizontal Sashes on two sides

APOGEE_CUSTOM

627

Fume Hood-10 Horizontal Sashes, flow input/0-10 Vdc output

APOGEE_CUSTOM

628

Fume Hood-615 with maximum flow Sash alert, 2 facevel setpoint

APOGEE_CUSTOM

629

Fume Hood-605 with a separate Vertical Sash

APOGEE_CUSTOM

630

Fume Hood - 2-position Controller

APOGEE_CUSTOM

631

Fume Hood- walk-in, no face area in lower sash

APOGEE_CUSTOM

632

Fume Hood - Dual combination

APOGEE_CUSTOM

639

Fume Hood - 603 with flow input 0-10 Vdc output

APOGEE_CUSTOM

643

Fume Hood - 603 with 2 facvel setpoints and sash alert

APOGEE_CUSTOM

645

Fume Hood - 605 with 2 facvel setpoints and sash alert

APOGEE_CUSTOM

647

Fume Hood - 607 with 2 facvel setpoints and sash alert

APOGEE_CUSTOM

650

Constant Volume Fume Hood Monitor - Slave Mode

APOGEE_LABS

651

Constant Volume Fume Hood Monitor

APOGEE_LABS

652

Fume Hood - 10 combination walk-in with maximum flow

APOGEE_CUSTOM

658

Fume Hood - 603 with maximum flow, sash alert, 2 facevel setpoints

APOGEE_CUSTOM

659

Fume Hood - 605 with maximum flow, sash alert, 2 facevel setpoints

APOGEE_CUSTOM

660

Fume Hood - 607 with maximum flow, sash alert, 2 facevel setpoints

APOGEE_CUSTOM

701

DPM - Single Sensor Operation, Healthcare Application

APOGEE_LABS

702

DPM - Dual Sensor Operation, Healthcare Application

APOGEE_LABS

703

DPM - Single Sensor Operation, Lab Application

APOGEE_LABS

704

DPM - Dual Sensor Operation, Lab Application

APOGEE_LABS

710

Digital Energy Monitor Ser. 1000, 100A Small CT

APOGEE_LABS

711

Digital Energy Monitor Ser. 1000, 300A Small CT

APOGEE_LABS

712

Digital Energy Monitor Ser. 1000, 400A Medium CT

APOGEE_LABS

713

Digital Energy Monitor Ser. 1000, 800A Medium CT

APOGEE_LABS

714

Digital Energy Monitor Ser. 1000, 800A Large CT

APOGEE_LABS

715

Digital Energy Monitor Ser. 1000, 1600A Large CT

APOGEE_LABS

716

Digital Energy Monitor Ser. 1000, 2400A Large CT

APOGEE_LABS

717

Digital Energy Monitor S2000, 100A, Small CT

APOGEE_LABS

718

Digital Energy Monitor S2000, 300A, Small CT

APOGEE_LABS

719

Digital Energy Monitor S2000, 400A, Medium CT

APOGEE_LABS

721

Digital Energy Monitor S2000, 800A, Large CT

APOGEE_LABS

722

Digital Energy Monitor S1600, 2400A, Large CT

APOGEE_LABS

723

Digital Energy Monitor S2000, 2400A, Large CT

APOGEE_LABS

790

DPM - Slave Mode

APOGEE_LABS

900

FHC, 8 Horizontal Walk-in - Slave Mode

APOGEE_LABS

903

Fume Hood - Single/Multi-Vertical Sash with Damper

APOGEE_LABS

905

Fume Hood - Horizontal Sash with Damper

APOGEE_LABS

907

Fume Hood - Combination Sash with Damper

APOGEE_LABS

920

Fume Hood - 903 with Auto Zero

APOGEE_CUSTOM

921

Fume Hood - 905 with Auto Zero

APOGEE_CUSTOM

922

Fume Hood - 907 with Auto Zero

APOGEE_CUSTOM

923

Fume Hood - 903 with AO2 = Actual Flow

APOGEE_CUSTOM

924

Fume Hood - 905 with AO2 = Actual Flow

APOGEE_CUSTOM

925

Fume Hood - 907 with AO2 = Actual Flow

APOGEE_CUSTOM

926

Fume Hood - 903 for Venturi Air Valve

APOGEE_CUSTOM

927

Fume Hood - 905 for Venturi Air Valve

APOGEE_CUSTOM

928

Fume Hood - 907 for Venturi Air Valve

APOGEE_CUSTOM

929

FHC/8 Horizontal Walk-in, 2 Vertical Heights with FS19

APOGEE_CUSTOM

929

FHC/Damper, 8 Horizontal Walk-in, 2 Vertical Heights

APOGEE_CUSTOM

930

FHC/Damper, Dual Combination

APOGEE_LABS

933

FHC/Vent, 8 Horizontal Walk-in, 2 Vertical Heights

APOGEE_CUSTOM

934

FHC Application 905 with Differential Horizontal Sash Widths

APOGEE_CUSTOM

935

FHC Application 907 with Differential Horizontal Sash Widths

APOGEE_CUSTOM

940

Constant Volume, 2-Position Fume Hood

APOGEE_LABS

941

FHC/Damper, 8 Horizontal Walk-in, 2 Vertical Height/Differential Widths

APOGEE_LABS

942

FHC/Vent, 8 Horizontal Walk-in, 2 Vertical Height/Differential Widths

APOGEE_LABS

2020

VAV Cooling Only

APOGEE_P1

2021

VAV Cooling or Heating

APOGEE_P1

2022

VAV with Electric Reheat

APOGEE_P1

2023

VAV with Hot Water Reheat

APOGEE_P1

2024

VAV Series Fan Powered with Electric Reheat

APOGEE_P1

2025

VAV Series Fan Powered with Hot Water Reheat

APOGEE_P1

2026

VAV Parallel Fan Powered with Electric Reheat

APOGEE_P1

2027

VAV Parallel Fan Powered with Hot Water Reheat

APOGEE_P1

2030

Constant Volume Cooling Only

APOGEE_P1

2032

Constant Volume with Electric Reheat

APOGEE_P1

2033

Constant Volume with Hot Water Reheat

APOGEE_P1

2035

DD Constant Volume 2 Inlet Damper Acts with optional Reheat

APOGEE_P1

2036

DD Constant Volume 1 Inlet 1 Outlet Damper with optional Reheat

APOGEE_P1

2040

VAV Pressure Dependent Cooling or Heating

APOGEE_P1

2041

VAV Pressure Dependent with 1 or 2 Valve Hot Water Reheat

APOGEE_P1

2050

Fan Coil Unit 2-pipe Cool/Heat with optional Heating Valve

APOGEE_P1

2051

Fan Coil Unit Cooling and Heating

APOGEE_P1

2052

Fan Coil Unit 2-stage Cooling and Electric Reheat

APOGEE_P1

2053

Fan Coil Unit 2-stage Cooling and Hot Water Reheat

APOGEE_P1

2054

Fan Coil Unit Cooling and Electric Heat

APOGEE_P1

2064

DD VAV 2 Position Hot/Cold Damper and Volume Damper with optional Reheat

APOGEE_P1

2065

DD VAV 2 Inlet Damper Actuators with optional Reheat

APOGEE_P1

2066

DD VAV 1 Inlet 1 Outlet Damper Actuator with optional Reheat

APOGEE_P1

2070

Heat Pump 1 Compressor with Reversing Valve Control

APOGEE_P1

2071

Heat Pump 2 Compressor with Reverse Valve Control

APOGEE_P1

2072

Heat Pump Heat/Cool without Reverse Valve Control

APOGEE_P1

2090

Unit Cond. with Pot Control of Damper - Slave Mode

APOGEE_P1

2091

Slave Mode for VAV Application 2026 with modified fan

APOGEE_P1

2092

Constant Volume - Slave Mode with 2" WC

APOGEE_P1

2100

CV Hot Water RH, Humidity Control and Secure Mode

APOGEE_CUSTOM

2120

Cooling Only with Secure Mode

APOGEE_P1SEC

2121

VAV Cooling or Heating with Secure Mode

APOGEE_P1SEC

2122

Electric RH or Baseboard Heat and Secure Mode

APOGEE_P1SEC

2123

VAV with Hot Water Reheat and Secure Mode

APOGEE_P1SEC

2124

VAV Series Fan and Electric Heat and Secure Mode

APOGEE_P1SEC

2125

VAv Series Fan and Hot Water Reheat and Secure Mode

APOGEE_P1SEC

2126

VAV Parallel Fan with Electric Heat and Secure Mode

APOGEE_P1SEC

2127

VAV Parallel Fan with Hot Water Reheat and Secure Mode

APOGEE_P1SEC

2130

Part 11 Constant Volume Cooling Only

APOGEE_P1SEC

2132

Part 11 Constant Volume with Electric Reheat

APOGEE_P1SEC

2133

Part 11 Constant Volume with Hot Water Reheat

APOGEE_P1SEC

2140

Part 11 VAV Pressure Dependent Cooling or Heating

APOGEE_P1SEC

2141

Part 11 VAV Pressure Dependent with 1 - 2 Valve Hot Water Reheat

APOGEE_P1SEC

2150

Part 11 Fan Coil Unit 2-pipe Cool/Heat Optional Heating Valve

APOGEE_P1SEC

2151

Part 11 Fan Coil Unit Cooling and Heating

APOGEE_P1SEC

2152

Part 11 Fan Coil Unit 2-stage Cooling and Electric Reheat

APOGEE_P1SEC

2153

Part 11 Fan Coil Unit 2-stage Cooling and Hot Water Reheat

APOGEE_P1SEC

2154

Part 11 Fan Coil Unit Cooling and Electric Heat

APOGEE_P1SEC

2188

Part 11 Fan Coil Unit Conditioner - Slave Mode

APOGEE_P1SEC

2190

CV Controller with Secure Mode - Slave Mode

APOGEE_P1SEC

2191

VAV with Secure Mode - Slave Mode

APOGEE_P1SEC

2192

Part 11 Constant Volume Controller - Slave Mode

APOGEE_P1SEC

2197

TEC with Expanded I/O Capability and Secure Mode

APOGEE_CUSTOM

2215

RPC Pneumatic CAV with Hot Water Reheat and VAV Switchover

APOGEE_LABS

2216

RPC Electronic VAV with Hot Water Reheat

APOGEE_LABS

2217

RPC Pneumatic VAV with Hot Water Reheat

APOGEE_LABS

2218

RPC Electronic CAV with Hot Water Reheat

APOGEE_LABS

2219

RPC Pneumatic CAV with Hot Water Reheat

APOGEE_LABS

2237

DD Const Vol 2 Inlet Sensors with optional Reheat

APOGEE_P1

2238

DD Const Vol 1 Inlet 1 Outlet Sensor with optional Reheat

APOGEE_P1

2267

DD VAV 2 Inlet Sensors with optional Reheat

APOGEE_P1

2268

DD VAV 1 Inlet 2 Outlet Sensor with optional Reheat

APOGEE_P1

2269

DD VAV with Hot Duct to second Cold Duct Changeover

APOGEE_P1

2273

Heat Pump Multi-Stage with Reverse Valve Control

APOGEE_P1

2274

Heat Pump Multi-Stage without Reverse Valve Control

APOGEE_P1

2276

Unit Vent Heat Pump with Reverse Valve and Cycles I, II

APOGEE_CUSTOM

2277

Unit Vent Heat Pump with Reverse Valve and Cycle III

APOGEE_CUSTOM

2278

Unit Vent Heat Pump without Reverse Valve and Cycles I, II

APOGEE_CUSTOM

2279

Unit Vent Heat Pump without Reverse Valve and Cycle III

APOGEE_CUSTOM

2281

Unit Vent 0-10V Heating/Cooling Cycles I, II

APOGEE_P1

2283

Unit Vent 0-10V Heating/Cooling Cycle III

APOGEE_P1

2284

Unit Vent 0-10V Heating/DX Cycles I, II

APOGEE_P1

2286

Unit Vent 0-10V Heating/DX Cycle III

APOGEE_P1

2287

Unit Vent 0-10V Heating/Cooling/DX Cycle W

APOGEE_P1

2290

Heat Pump Multi-Stage - Slave Mode

APOGEE_P1

2293

Dual Duct VAV with Ventilation - Slave Mode

APOGEE_P1

2294

Lab Press Controller - Slave Mode

APOGEE_LABS

2295

CAV Pneumatic with 0-10V Flow - Slave Mode

APOGEE_P1

2299

VAV w/CW 2-position. OA Damper and Static Pressure – Slave Mode

APOGEE_P1

2300

Constant Volume with Hot Water Reheat and Humidity Control

APOGEE_CUSTOM

2301

VAV with Hot Water Reheat and Humidity Control

APOGEE_CUSTOM

2302

Relative Humidity Control Using Specific Humidity

APOGEE_CUSTOM

2303

Relative Humidity Control

APOGEE_CUSTOM

2304

VAV with 2-speed Series Fan, Hot Water Valve, Discharge Flow Monitor

APOGEE_CUSTOM

2305

VAV with 2-speed Series Fan, Electric Heating, Discharge Flow Monitor

APOGEE_CUSTOM

2306

Unit Vent with Relative Humidity Control and Hot Water Heating

APOGEE_CUSTOM

2307

Unit Vent with Dew Point Temperature Control and Hot Water Heating

APOGEE_CUSTOM

2308

VAV with CHW, Hot Water, Econ Cycle, Static Pressure Control

APOGEE_CUSTOM

2309

VAV with CHW, Electric Heat, Econ Cycle, Static Pressure Control

APOGEE_CUSTOM

2310

VAV with DX, Electric/RC Heat, Static Pressure Control, Dumpback Damper

APOGEE_CUSTOM

2311

CAV with CHW, Hot Water, Econ Cycle, CO2 Sensor

APOGEE_CUSTOM

2312

CAV with CHW, Electric Heat, Econ Cycle, CO2 Sensor

APOGEE_CUSTOM

2313

CAV with DX, Electric or RC Hot Water, Econ Cycle, CO2 Sensor

APOGEE_CUSTOM

2314

Constant Volume Cooling Only with No Damper Calibration

APOGEE_CUSTOM

2315

Constant Volume Electric Reheat with No Damper Calibration

APOGEE_CUSTOM

2316

RPC Electronic VAV with Hot Water Reheat and No Damper Calibration

APOGEE_CUSTOM

2317

Constant Volume Hot Water Reheat with No Damper Calibration

APOGEE_CUSTOM

2318

RPC Electronic CAV with Hot Water Reheat and No Damper Calibration

APOGEE_CUSTOM

2319

Unit Vent with Relative Humidity Control and Electric Heating

APOGEE_CUSTOM

2320

VAV Fan with Flow, Temperature, and Static Pressure Control

APOGEE_CUSTOM

2321

VAV Fan with Flow and Temperature Control

APOGEE_CUSTOM

2322

RPC Pneumatic CAV with BTU Compensation

APOGEE_CUSTOM

2323

Fan Coil with 6-stages of Electric Reheat

APOGEE_CUSTOM

2324

Fan Coil with 6-stages of Cooling

APOGEE_CUSTOM

2326

Heat Pump 1 Compressor with Reverse Valve and Dehumidification

APOGEE_CUSTOM

2327

Unit Vent with 2-DX Cycle III

APOGEE_CUSTOM

2328

VAV with Hot Water Reheat and SCR Fan

APOGEE_CUSTOM

2329

VAV Series Fan Powered with 2-speed Fan and Electric Reheat

APOGEE_CUSTOM

2330

CAV Pneumatic with 0-10V Flow

APOGEE_CUSTOM

2332

LRC with BTU Compensation

APOGEE_CUSTOM

2333

VAV with Induction Damper

APOGEE_CUSTOM

2334

Unit Vent with FBD, Heating and DX Cooling ASHRAE Cycle 1 &2

APOGEE_CUSTOM

2335

VAV with Dehumidification

APOGEE_CUSTOM

2336

RPC Electronic VAV with Hot Water Reheat and Humidity Control

APOGEE_CUSTOM

2337

VAV with CW, 2-position OA Damper and Static Pressure

APOGEE_CUSTOM

2338

RPC Electronic CAV with Hot Water Reheat and Humidity Control

APOGEE_CUSTOM

2339

Fan Coil Dual Zone Unit 2-pipe Cool/Heat

APOGEE_CUSTOM

2341

Unit Vent Controller with Mixed Air Sequence

APOGEE_CUSTOM

2342

Unit Vent with Mixed Air Sequence and DX Cooling

APOGEE_CUSTOM

2343

LRC Pneumatic Application 2343

APOGEE_CUSTOM

2344

LRC Pneumatic Application 2344

APOGEE_CUSTOM

2345

LRC Pneumatic Application 2343

APOGEE_CUSTOM

2346

Fan Coil with 3-speed Fan and Dehumidification

APOGEE_CUSTOM

2347

Fan Coil 4-Pipe with 3-Speed Fan

APOGEE_CUSTOM

2348

Unit Vent Controller with Free Cooling, Night Purge and Dehumidification, 0-10V Output

APOGEE_CUSTOM

2349

Unit Vent Controller with Free Cooling, Night Purge and Dehumidification

APOGEE_CUSTOM

2352

Unit Vent with Mixed Air and Dehumidification

APOGEE_CUSTOM

2353

Unit Vent with Mixed Air and Dehumidification

APOGEE_CUSTOM

2354

Unit Vent with Heat and/or CW Cool and Cycles I, II

APOGEE_CUSTOM

2355

Unit Vent with Heat and/or CW Cool and Cycle III

APOGEE_CUSTOM

2356

Unit Vent w/Heat and DX Cooling and Cycles I, II

APOGEE_CUSTOM

2357

Unit Vent with Heat and DX Cooling and Cycle III

APOGEE_CUSTOM

2358

Fan Coil 4-pipe with 2–speed Fan

APOGEE_CUSTOM

2359

Dual Duct VAV with Ventilation

APOGEE_CUSTOM

2360

VAV with CO2 Monitoring - Cooling Only

APOGEE_CUSTOM

2361

VAV with CO2 Monitoring - Cooling and Heating

APOGEE_CUSTOM

2362

VAV with CO2 Monitoring - Electric Heat or Baseboard Radiation

APOGEE_CUSTOM

2363

VAV with CO2 Monitoring - Hot Water Reheat

APOGEE_CUSTOM

2364

VAV with CO2 Monitoring - Fan Powered with Electric Reheat

APOGEE_CUSTOM

2365

VAV with CO2 Monitoring - Fan Powered with Hot Water Reheat

APOGEE_CUSTOM

2366

VAV with CO2 Monitoring - Parallel Fan Powered with Electric Reheat

APOGEE_CUSTOM

2367

VAV with CO2 Monitoring - Parallel Fan Powered with Hot Water Reheat

APOGEE_CUSTOM

2368

CV RPC with Hot Water Reheat, Relative Humidity and 3–position Switch

APOGEE_CUSTOM

2369

VAV with Revised Fan Operation

APOGEE_CUSTOM

2370

VAV with Expanded Room Temperature Range - Cooling Only

APOGEE_CUSTOM

2371

VAV with Expanded Room Temperature Range - Cooling and Heating

APOGEE_CUSTOM

2372

VAV with Expanded Room Temperature Range-Electric Heat or Baseboard Radiation

APOGEE_CUSTOM

2373

VAV with Expanded Room Temperature Range - Hot Water Reheat

APOGEE_CUSTOM

2374

VAV with Expanded Room Temperature Range - Fan Powered with Electric Reheat

APOGEE_CUSTOM

2375

VAV with Expanded Room Temperature Range - Fan Powered with Hot Water Reheat

APOGEE_CUSTOM

2376

VAV with Expanded Room Temperature Range - Parallel Fan Powered with Electric Reheat

APOGEE_CUSTOM

2377

VAV with Expanded Room Temperature Range - Parallel Fan Powered with Hot Water Reheat

APOGEE_CUSTOM

2378

Unit Condoner With Potentiometer Control of Damper

APOGEE_CUSTOM

2380

Slave Mode

APOGEE_P1

2381

RPC Pneumatic with BTU Compensation - Slave Mode

APOGEE_LABS

2382

VAV with Dehumidification - Slave Mode

APOGEE_P1

2383

LRC Pneumatic Application 2383 - Slave Mode

APOGEE_LABS

2384

UV 2–position Hot Water and Modulating Cold Water Valves - Slave Mode

APOGEE_P1

2385

VAV with CO2 Monitoring - Slave Mode

APOGEE_P1

2387

RPC Pneumatic with Humidity and 3–position Switch - Slave Mode

APOGEE_LABS

2390

Relative Humidity Controller - Slave Mode

APOGEE_P1

2391

VAV with Hot Water Reheat and Humidity Control - Slave Mode

APOGEE_P1

2393

Australian SPC - Slave Mode

APOGEE_P1

2394

RPC Electronic with Humidity Control - Slave Mode

APOGEE_LABS

2396

Constant Volume with No Damper Cal - Slave Mode

APOGEE_P1

2397

CAV Box Fan Coil Controller with optional VIV - Slave Mode

APOGEE_P1

2398

Unit Vent with Humidity Control - Slave Mode

APOGEE_P1

2399

Heat Pump 1 Cmpr and Dehumidification - Slave Mode

APOGEE_P1

2400

Fan Coil with DI Pulse Accumulator

APOGEE_CUSTOM

2401

VAV Series Fan Powered Cooling Control

APOGEE_P1

2402

LRC Electric with BTU Compensation

APOGEE_CUSTOM

2403

VAV with Revised Fan Logic

APOGEE_CUSTOM

2404

Fan Coil 2-pipe with 3–speed Fan

APOGEE_CUSTOM

2406

Unit Conditioner Cooling with Motion Sensor

APOGEE_CUSTOM

2408

Static Pressure Controller

APOGEE_CUSTOM

2409

Fan Coil with Fan Proof, Dis Temperature Alarm and Cond Alarm

APOGEE_CUSTOM

2410

Lab Room Controller for the Venturi Valve

APOGEE_LABS

2411

Asia Pacific 3–speed Fan Coil Controller

APOGEE_CUSTOM

2412

Unit Vent with Modulating Face and Bypass Control

APOGEE_CUSTOM

2413

Hines VAV with Variable Speed Series Fan, Electric Heat

APOGEE_CUSTOM

2414

VAV Parallel Fan Powered with Electric Reheat and Modified Damper Sequence

APOGEE_P1

2415

VAV with Calibratable RTD

APOGEE_CUSTOM

2416

VAV Room Pressure Controller with Hot Water Reheat and 2" WC

APOGEE_CUSTOM

2417

CAV with Calibratable RTD

APOGEE_CUSTOM

2418

CV Room Pressure Controller with HW Reheat and 2" WC

APOGEE_LABS

2419

Fan Coil with Calibratable third–party RTD

APOGEE_CUSTOM

2420

VAV Cooling Only 2" WC

APOGEE_CUSTOM

2421

VAV Cooling or Heating 2" WC

APOGEE_CUSTOM

2422

VAV with Electric Reheat of Baseboard Radiation 2" WC

APOGEE_CUSTOM

2423

VAV with Hot Water Reheat 2" WC

APOGEE_CUSTOM

2424

VAV Series Fan Powered with Electric Reheat 2" WC

APOGEE_CUSTOM

2425

VAV Series Fan Powered with Hot Water Reheat 2" WC

APOGEE_CUSTOM

2426

VAV Parallel Fan Powered with Electric Reheat 2" WC

APOGEE_CUSTOM

2427

VAV Parallel Fan Powered with Hot Water Reheat 2" WC

APOGEE_CUSTOM

2428

Fan Coil with Calibratable RTD

APOGEE_CUSTOM

2429

Series Fan VAV – Option for 0-10V Fan Speed Control with Hot Water Reheat, Spare AIs and AOVs, Optional Night Damper, and 2 AVS

APOGEE_CUSTOM

2430

Constant Volume Cooling Only with 2" WC

APOGEE_CUSTOM

2431

Disch Temperature Control with Room-Load Heat/Cool Switchover

APOGEE_CUSTOM

2432

Constant Volume with Electric Reheat and 2" WC

APOGEE_CUSTOM

2433

Constant Volume with Hot Water Reheat and 2" WC

APOGEE_CUSTOM

2434

Fan Coil Unit with 3–stage Cooling and Hot Water Heat

APOGEE_CUSTOM

2435

Fan Coil Unit Cooling and Electric Heat with Pulse Counter

APOGEE_CUSTOM

2436

Pulse Counter

APOGEE_CUSTOM

2437

LRC with GDE 131 Actuation - Single Blade VAV

APOGEE_CUSTOM

2438

LRC with GDE 161 Actuation and Venturi Air Valve

APOGEE_CUSTOM

2439

LRC with GDE 161 Actuation - VFD Sup and Venturi Exhaust

APOGEE_LABS

2448

Unit Vent Heating/Cooling with Floating Outputs

APOGEE_CUSTOM

2449

LRC with Vortex Shedding and Analog Actuators

APOGEE_CUSTOM

2450

VAV Parallel Fan, Hot Water Reheat with AZM on DO5

APOGEE_P1

2451

LRC Slow Actuation with BTU Compensation

APOGEE_CUSTOM

2452

VAV Application 2026 with Modified Fan Operation

APOGEE_CUSTOM

2453

LRC Dual Duct VAV/CV with BTU Compensation

APOGEE_CUSTOM

2455

UV 2 position Hot Water and Modulating Cold Water Valves

APOGEE_CUSTOM

2456

LRC Venturi with BTU Compensation

APOGEE_CUSTOM

2457

VAV VSD Series Fan and 3–stage Electric Heat

APOGEE_CUSTOM

2458

LRC VAV GDE Actuation on OAVS

APOGEE_CUSTOM

2459

Slave Mode LRC, Slow Actuation

APOGEE_CUSTOM

2460

Water to Air Heat Pump with 1-stage Electric Heat, Multi-Speed Fan and Motion Sensor

APOGEE_CUSTOM

2461

Lighting Ctrl with Low Voltage Pulsed Relays

APOGEE_CUSTOM

2462

Lighting Ctrl with Low Voltage Maintained Relays

APOGEE_CUSTOM

2463

Pressurized Room Controller (PRC)

APOGEE_CUSTOM

2464

VAV - CO2 Alarming, HW Reheat and Radiation

APOGEE_CUSTOM

2465

Pressurized Room Controller (PRC) – Slave Mode

APOGEE_LABS

2466

Lighting Ctrl with Low Voltage Relays – Slave Mode

APOGEE_P1

2468

LRC, Slow Actuation on OAVS Hot Water

APOGEE_LABS

2469

VAV VSD Series Fan - Slave Mode

APOGEE_P1

2470

LRC Venturi with BTU Compensation - Slave Mode

APOGEE_LABS

2472

LRC Dual Duct VAV/CV with BTU Compensation - Slave Mode

APOGEE_LABS

2473

VAV Terminal Box Controller - Slave Mode

APOGEE_ATEC

2474

LRC Slow Actuation with BTU Compensation - Slave Mode

APOGEE_LABS

2475

LRC with Vortex Shedding and Analog Act - Slave Mode

APOGEE_LABS

2476

Unit Vent Heating/Cooling with Floating Outputs - Slave Mode

APOGEE_P1

2477

LRC with GDE 131 Actuation - Slave Mode

APOGEE_LABS

2478

LRC with GDE 161 Actuation and Venturi - Slave Mode

APOGEE_LABS

2479

LRC with GDE 161 Actuation - VFD Sup - Slave Mode

APOGEE_LABS

2481

VAV with Calibratable RTD - Slave Mode

APOGEE_P1

2482

CAV with Calibratable RTD - Slave Mode

APOGEE_P1

2483

Fan Coil with Calibratable RTD - Slave Mode

APOGEE_P1

2484

Hines VAV with Variable Speed Ser Fan, Electric Heat - Slave Mode

APOGEE_P1

2485

FCU with 3–stage Cooling and Hot Water Heat - Slave Mode

APOGEE_P1

2486

COVAV Demo Application 2486

APOGEE_ATEC

2488

VAV with 0-10V Series-Fan Speed and Hot Water Reheat - Slave Mode

APOGEE_P1

2490

Fan Coil with DI Pulse Accumulator - Slave Mode

APOGEE_P1

2491

Static Pressure Controller - Slave Mode

APOGEE_P1

2492

FC with Fan Proof, Dis Temperature Alarm, Cond Alarm - Slave Mode

APOGEE_P1

2495

Asia Pacific 3–speed Fan Coil Controller - Slave Mode

APOGEE_P1

2497

TEC with Expanded Point I/O

APOGEE_CUSTOM

2499

VAV - CO2 Alarming, Hot Water Reheat and Radiation – Slave Mode

APOGEE_P1

2500

VAV Cooling Only

APOGEE_ATEC

2501

VAV Cooling or Heating

APOGEE_ATEC

2502

CV AHU with 2–position 100% OA Damper, SA temperature, Cold Water Cooling/Hot Water Heating

APOGEE_CUSTOM

2503

CV AHU with 2–position 100% OA Damper, Cold Water Cooling/Hot Water Heating

APOGEE_CUSTOM

2510

VAV Cooling Only

APOGEE_BTEC

2511

VAV Cooling and Heating

APOGEE_BTEC

2512

VAV with Electric Heat or Baseboard Radiation

APOGEE_BTEC

2513

VAV with Hot Water Heat

APOGEE_BTEC

2514

VAV Series Fan and Electric Heat

APOGEE_BTEC

2515

VAV Series or Parallel Fan and Hot Water Reheat

APOGEE_BTEC

2516

VAV Parallel Fan and Electric Heat

APOGEE_BTEC

2517

VAV with Hot Water Heat and Parallel Fan

APOGEE_BTEC

2520

COVAV Demo Application 2520

APOGEE_ATEC

2521

COVAV Demo Application 2521

APOGEE_ATEC

2522

VAV with Electric Reheat

APOGEE_ATEC

2523

VAV with Hot Water Reheat

APOGEE_ATEC

2524

VAV Series Fan Powered with Electric Reheat

APOGEE_ATEC

2526

VAV Parallel Fan Powered with Electric Reheat

APOGEE_ATEC

2528

VAV Pressure Dependent Cooling or Heating

APOGEE_BTEC

2529

VAV Pressure Dependent with 1 or 2 Valve Hot Water Reheat

APOGEE_BTEC

2530

VAV Cooling Only

APOGEE_BTEC

2531

VAV Cooling or Heating

APOGEE_BTEC

2532

VAV with Electric Reheat

APOGEE_BTEC

2533

VAV with Hot Water Reheat

APOGEE_BTEC

2534

VAV Series Fan Powered with Electric Reheat

APOGEE_BTEC

2535

VAV Series Fan Powered with Hot Water Reheat

APOGEE_BTEC

2536

VAV Parallel Fan Powered with Electric Reheat

APOGEE_BTEC

2537

VAV Parallel Fan Powered with Hot Water Reheat

APOGEE_BTEC

2540

Unit Cond VAV Pressure Dependent Cooling or Heating

APOGEE_BTEC

2541

Unit Cond VAV Pressure Dependent Hot Water Reheat

APOGEE_BTEC

2542

Fan Coil Unit 2-pipe Cool/Heat with Optional Heating Valve

APOGEE_BTEC

2543

Fan Coil Unit Cooling and Heating

APOGEE_BTEC

2544

Fan Coil Unit 2-stage Cooling and Electric Reheat

APOGEE_BTEC

2545

Fan Coil Unit 2-stage Cooling and Hot Water Reheat

APOGEE_BTEC

2546

Fan Coil Unit Cooling and Electric Heat

APOGEE_BTEC

2549

BACnet Heat Pump – Slave Mode

APOGEE_BTEC

2550

Fan Coil Cooling and Heating

APOGEE_BTEC

2551

Fan Coil Cooling and Heating

APOGEE_BTEC

2552

Fan Coil Cooling and Electric Heat

APOGEE_BTEC

2553

Fan Coil 2–stage Cooling and Hot Water Reheat

APOGEE_BTEC

2554

Fan Coil Cooling and Electric Heat

APOGEE_BTEC

2557

VAV VSD Series Fan and 3–stage Electric Heat

APOGEE_CUSTOM

2558

BCNT VAV DCV (CO2) and Chilled Beam

APOGEE_CUSTOM

2560

VAV Cooling Only

APOGEE_ATEC

2561

VAV Cooling or Heating

APOGEE_ATEC

2562

VAV with Electric Reheat

APOGEE_ATEC

2563

VAV with Hot Water Reheat

APOGEE_ATEC

2564

VAV Series Fan Powered with Electric Reheat

APOGEE_ATEC

2565

VAV Series Fan Powered with Hot Water Reheat

APOGEE_ATEC

2566

VAV Parallel Fan Powered with Electric Reheat

APOGEE_ATEC

2567

VAV Parallel Fan Powered with Hot Water Reheat

APOGEE_ATEC

2573

Heat Pump Multi-Stage with Reversing Valve Control

APOGEE_BTEC

2574

Heat Pump Multi-Stage without Reversing Valve Control

APOGEE_BTEC

2575

BCNT UV Heating Cold Water Cooling ASHRAE Cycle I, II

APOGEE_BTEC

2576

BCNT UV Heating Cold Water Cooling ASHRAE Cycle III

APOGEE_BTEC

2577

BCNT UV Heating DX Cooling ASHRAE Cycle I and II

APOGEE_BTEC

2578

BCNT UV Heating DX Cooling ASHRAE Cycle III

APOGEE_BTEC

2579

BCNT UV Heating Cooling NESBITT Cycle W

APOGEE_BTEC

2580

VAV CO2 with AOV or Floating Heat

APOGEE_CUSTOM

2581

VAV Series Fan with CO2, AOV or Floating Heat

APOGEE_CUSTOM

2582

VAV Parallel Fan with CO2, AOV or Floating Heat

APOGEE_CUSTOM

2583

BCNT HP MultiCompr Mixed Air Reverse Valve Control

APOGEE_CUSTOM

2584

BCNT HP HtgClg with Mixed Air and Internal Reverse Valve

APOGEE_CUSTOM

2585

Fan Coil Unit Conditioner - Slave Mode

APOGEE_BTEC

2586

VAV Terminal Box Controller - Slave Mode

APOGEE_BTEC

2587

TEC - Slave mode Electronic Output with Secure Mode

APOGEE_BTEC

2588

CV AHU with 2 Position 100% OA Damper - Slave Mode

APOGEE_BTEC

2590

Heat Pump Multi-Stage - Slave Mode

APOGEE_BTEC

2591

Unit Conditioner - Slave Mode

APOGEE_BTEC

2592

Slave Mode BCNT VAV DCV (CO2) Chill Beam

APOGEE_LABS

2593

BCNT HP MultiCompr Mixed Air Reverse Valve Control

APOGEE_BTEC

2594

BCNT HP HtgClg with Mixed Air and Internal Reverse Valve

APOGEE_BTEC

2595

BACnet Unit Vent - Slave Mode

APOGEE_BTEC

2596

TEC with Expanded Point I/O

APOGEE_BTEC

2597

VAV Terminal Box Controller - Slave Mode

APOGEE_ATEC

2598

BACnet VAV with CO2 Monitoring

APOGEE_BTEC

2599

VAV VSD Series Fan - Slave Mode

APOGEE_BTEC

2600

Slave Mode

APOGEE_LABS

2601

VAV with Reheat - One Exhaust, One Supply

APOGEE_LABS

2602

VAV with Reheat - No Exhaust, One or Two Supplies

APOGEE_LABS

2603

VAV Dual-Duct - One Exhaust, One Supply

APOGEE_LABS

2611

VAV with Reheat - One Exhaust, One Supply

APOGEE_LABS

2612

VAV with Reheat - No Exhaust, One or Two Supplies

APOGEE_LABS

2613

VAV Dual-Duct - One Exhaust, One Supply

APOGEE_LABS

2620

LRC VAV Room Pressurization with Hot Water Reheat and Two Venturi Valves

APOGEE_LABS

2621

VAV Room Pressurization with Hot Water Reheat - One Exhaust, One Supply

APOGEE_LABS

2622

VAV Room Pressurization with Hot Water Reheat and Slow Venturi Air Valves, One Exhaust, One Supply

APOGEE_LABS

2623

LCM-OAVS Damper Slow RTS

APOGEE_LABS

2624

LCM-OAVS with Slow Supply Damper Actuation and Slow Exhaust Venturi Air Valve

APOGEE_LABS

2626

LRC VAV with Hot Water Reheat, BTU Compensation and Two Venturi Valves

APOGEE_LABS

2627

VAV Room Press with BTU Compensation, Hot Water Reheat and Fast Actuation

APOGEE_LABS

2628

VAV Room Pressurization with Hot Water Reheat and Slow Venturi Air Valves, One Exhaust, One Supply - includes BTU Compensation

APOGEE_LABS

2629

LCM-OAVS Damper Slow BTU

APOGEE_LABS

2630

LCM-OAVS with Slow Supply Damper Actuation and Slow Exhaust Venturi Air Valve - includes BTU Compensation

APOGEE_LABS

2631

PRC-OAVS with Pressurization Control by Differential Flow Reset, with Heating by BTU Compensation - Slow Actuation, Floating or Analog Output

APOGEE_LABS

2697

LCM-OAVS Damper Slow RTS/BTU - Slave Mode

APOGEE_LABS

2698

VAV Room Press with Hot Water Reheat - Slave Mode

APOGEE_LABS

2699

LRC VAV Room Press for Venturi Valves - Slave Mode

APOGEE_LABS

2700

ABB ACH 500 Adjustable Frequency AC Drive

APOGEE_INT

2701

MagneTek GPD 505 Adjustable Frequency AC Drive

APOGEE_INT

2703

Graham VLT 3500 Adjustable Frequency AC Drive

APOGEE_INT

2705

Square D ALTIVAR 66 Adjustable Frequency AC Drive

APOGEE_INT

2706

Saftronics FP5 Adjustable Frequency AC Drive

APOGEE_INT

2707

ABB ACS 600 Adjustable Frequency AC Drive

APOGEE_INT

2708

ABB ACH 400 Adjustable Frequency AC Drive

APOGEE_INT

2709

VLT6000 HVAC

APOGEE_INT

2710

Reliance VTAC 7 Adjustable Frequency AC Drive

APOGEE_INT

2711

GE/Fuji AF$300 Adjustable Frequency AC Drive

APOGEE_INT

2712

Magnetek GPD 506 VFD

APOGEE_INT

2713

HV9000 VFD

APOGEE_INT

2714

Toshiba E3 Adjustable Frequency AC Drive

APOGEE_INT

2715

SquareD Altivar 58

APOGEE_INT

2717

SIEMENS ECO VSD

APOGEE_INT

2718

Rockwell/Reliance VTAC9 VFD

APOGEE_INT

2719

ABB ACH400 VSD Direct Connect

APOGEE_INT

2720

GE Fuji AF-300 G11/P11 Adjustable AC Drive

APOGEE_INT

2721

Yaskawa Electric America E7

APOGEE_INT

2722

SIEMENS SED2

APOGEE_INT

2723

ABB ACS 600 VSD

APOGEE_INT

2724

ABB ACH 400 VSD

APOGEE_INT

2726

AC Tech MCH Variable Speed AC Drive

APOGEE_INT

2728

Hitachi L300P Series Inverter

APOGEE_INT

2729

Hitachi L100 Series Inverter Drive

APOGEE_INT

2730

Hitachi J300 Series Inverter Drive

APOGEE_INT

2731

Eurotherm HVAC10 AC Drive/690+ Series

APOGEE_INT

2732

TB Wood WF2 Sensorless Vector Drive

APOGEE_INT

2733

GE Fuji AF-300 F11 Adjustable AC Drive

APOGEE_INT

2734

ABB ACH550 Frequency Drive

APOGEE_INT

2735

Allen Bradley

APOGEE_INT

2736

Toshiba Q7 2736

APOGEE_INT

2737

E-Clipse Bypass Adjustable Frequency AC Drive Bypass Option

APOGEE_INT

2738

Toshiba VF-FS1

APOGEE_INT

2741

Mitsubishi F700

APOGEE_INT

2742

SIEMENS SED2

APOGEE_INT

2743

Cutler-Hammer SVX9000

APOGEE_INT

2744

ABB_ACS800

APOGEE_INT

2747

Lumisys Lighting

APOGEE_INT

2750

Mitsubishi XLTR200

APOGEE_INT

2759

DanFoss VLT F100

APOGEE_INT

2770

SI BT300 Frequency Drive

APOGEE_INT

2771

PM50A

APOGEE_INT

2772

PM1000A

APOGEE_INT

2773

PM100A

APOGEE_INT

2774

PM200A

APOGEE_INT

2775

PM400A

APOGEE_INT

2776

VULCAIN VA901TCO 2776

APOGEE_INT

2777

VALCAIN VA901TCO 2777

APOGEE_INT

2778

VALCAIN VA901TCO 2778

APOGEE_INT

2779

VULCAIN VA901TCO 2779

APOGEE_INT

2780

Litrol Lighting Control MLC48R38G

APOGEE_INT

2781

Litrol Lighting Control MLC46R24G24I

APOGEE_INT

2782

Litrol Lighting Control MLC46R48I

APOGEE_INT

2783

Litrol Lighting Control MLC48R40I

APOGEE_INT

2784

Litrol Lighting Control MLC46G48I

APOGEE_INT

2785

Litrol Lighting Control MLC48G40I

APOGEE_INT

2786

Litrol Lighting Control MLC46P48I

APOGEE_INT

2787

Litrol Lighting Control MLC48P40I

APOGEE_INT

2788

Litrol Lighting Control MLC48R24G12P

APOGEE_INT

2793

MSA ZGARD Sensor

APOGEE_INT

2794

VULCAIN VA901TCO 2794

APOGEE_INT

2803

UAP Paris Special, Single Duct

APOGEE_INT

2804

UAP Paris Special, Dual Duct

APOGEE_INT

2812

UAP Paris Special - Slave Mode

APOGEE_INT

2817

Lab Press Controller with Hot Water Reheat

APOGEE_LABS

2822

Lighting Control 2 Circuits with Electric Reheat

APOGEE_INT

2830

Lighting Control 3 Circuits with VAV

APOGEE_INT

2833

Lighting Control 3 Circuits with VAV and Hot Water Reheat

APOGEE_INT

2843

VAV 0-10 Heat and CO2 Monitor

APOGEE_CUSTOM

2845

VAV Series Fan AO Heat CO2

APOGEE_CUSTOM

2847

VAV Parallel Fan AO Heat CO2

APOGEE_CUSTOM

2849

BACnet Heat Pump Slave Mode

APOGEE_ATEC

2855

Fan Coil 2-pipe Htg/Clg with Optional Cooling Valve and Electric Heating

APOGEE_P1

2860

VAV Cooling Only

APOGEE_ATEC

2861

VAV Cooling or Heating

APOGEE_ATEC

2862

VAV with Electric Reheat

APOGEE_ATEC

2863

VAV with Hot Water Reheat

APOGEE_ATEC

2864

VAV Series Fan Powered with Electric Reheat

APOGEE_ATEC

2865

VAV Series Fan Powered with Hot Water Reheat

APOGEE_ATEC

2866

VAV Parallel Fan Powered with Hot Water Reheat

APOGEE_ATEC

2867

VAV Parallel Fan Powered with Hot Water Reheat

APOGEE_ATEC

2891

Lighting Controller - Slave Mode

APOGEE_P1

2893

BCNT HP MultiCompr Mixed Air Reverse Valve Control

APOGEE_ATEC

2894

BCNT HP HtgClg with Mixed Air and Internal Reverse Valve

APOGEE_ATEC

2897

VAV Terminal Box Controller - Slave Mode

APOGEE_ATEC

2899

VAV AO Heat and CO2 Monitor – Slave Mode

APOGEE_P1

2917

Lab Press Controller with Hot Water Reheat and Dew Point Sensor

APOGEE_LABS

4000

RTU General

APOGEE_INT

4001

RTU_DAC

APOGEE_INT

4002

RTU_SCC

APOGEE_INT

4003

SCUC

APOGEE_INT

4010

UV General ver 1

APOGEE_INT

4011

UV Model 0 ver 1

APOGEE_INT

4012

UV Model 2 ver 1

APOGEE_INT

4013

UV Model 3 ver 1

APOGEE_INT

4014

UV Model 4 ver 1

APOGEE_INT

4015

UV Model 5 ver 1

APOGEE_INT

4016

UV Model 6 ver 1

APOGEE_INT

4017

UV Model 7 ver 1

APOGEE_INT

4018

UV Model 8 ver 1

APOGEE_INT

4019

UV Model 9 ver 1

APOGEE_INT

4020

UV Model 10 ver1

APOGEE_INT

4021

UV Model 11 ver1

APOGEE_INT

4022

UV Model 12 ver1

APOGEE_INT

4023

UV Model 13 ver1

APOGEE_INT

4024

UV Model 14 ver1

APOGEE_INT

4025

UV Model 15 ver1

APOGEE_INT

4026

UV Model 16 ver1

APOGEE_INT

4027

UV Model 17 ver1

APOGEE_INT

4028

UV Model 18 ver1

APOGEE_INT

4029

Centrifugal

APOGEE_INT

4030

AC Global Scroll

APOGEE_INT

4031

AC Scroll

APOGEE_INT

4032

AC Global Screw

APOGEE_INT

4033

WC Global Scroll

APOGEE_INT

4034

Chiller General

APOGEE_INT

4050

ECO2

APOGEE_INT

4053

YT STD V2

APOGEE_INT

4054

YT SSS V2

APOGEE_INT

4055

YT VSD V2

APOGEE_INT

4056

YK STD V2

APOGEE_INT

4057

YK SSS V2

APOGEE_INT

4058

YK VSD V2

APOGEE_INT

4059

YCAS MSTR V2

APOGEE_INT

4060

YCAS SLV V2

APOGEE_INT

4061

YCWS V2

APOGEE_INT

4062

YCAL 2050

APOGEE_INT

4063

YCAL TEMP

APOGEE_INT

4064

YCAL SUCT

APOGEE_INT

4065

YR STD

APOGEE_INT

4066

YR SSS

APOGEE_INT

4067

YS STD

APOGEE_INT

4068

YS SSS

APOGEE_INT

4098

Comm Fail

APOGEE_INT

4099

Diagnostic

APOGEE_INT

4100

UV General ver 2

APOGEE_INT

4101

UV Model 0 ver 2

APOGEE_INT

4102

UV Model 2 ver 2

APOGEE_INT

4103

UV Model 3 ver 2

APOGEE_INT

4104

UV Model 4 ver 2

APOGEE_INT

4105

UV Model 5 ver 2

APOGEE_INT

4106

UV Model 6 ver 2

APOGEE_INT

4107

UV Model 7 ver 2

APOGEE_INT

4108

UV Model 8 ver 2

APOGEE_INT

4109

UV Model 9 ver 2

APOGEE_INT

4110

UV Model 10 ver2

APOGEE_INT

4111

UV Model 11 ver2

APOGEE_INT

4112

UV Model 12 ver2

APOGEE_INT

4113

UV Model 13 ver2

APOGEE_INT

4114

UV Model 14 ver2

APOGEE_INT

4115

UV Model 15 ver2

APOGEE_INT

4116

UV Model 16 ver2

APOGEE_INT

4117

UV Model 17 ver2

APOGEE_INT

4118

UV Model 18 ver2

APOGEE_INT

4120

RTU2 General

APOGEE_INT

4121

RTU2_DAC

APOGEE_INT

4122

RTU2_SCC

APOGEE_INT

4123

SCUC2

APOGEE_INT

4125

RTU V3 DAC

APOGEE_INT

4126

RTU V3 SCC

APOGEE_INT

4127

SCUC V3 DAC

APOGEE_INT

4128

SCUC V3 SCC

APOGEE_INT

4130

UV GEN V3 ENG

APOGEE_INT

4131

UV MOD 0 V3 ENG

APOGEE_INT

4132

UV MOD 2 V3 ENG

APOGEE_INT

4133

UV MOD 3 V3 ENG

APOGEE_INT

4134

UV MOD 4 V3 ENG

APOGEE_INT

4135

UV MOD 5 V3 ENG

APOGEE_INT

4136

UV MOD 6 V3 ENG

APOGEE_INT

4137

UV MOD 7 V3 ENG

APOGEE_INT

4138

UV MOD 8 V3 ENG

APOGEE_INT

4139

UV MOD 9 V3 ENG

APOGEE_INT

4140

UV MOD10 V3 ENG

APOGEE_INT

4141

UV MOD11 V3 ENG

APOGEE_INT

4142

UV MOD12 V3 ENG

APOGEE_INT

4143

UV MOD13 V3 ENG

APOGEE_INT

4144

UV MOD14 V3 ENG

APOGEE_INT

4145

UV MOD15 V3 ENG

APOGEE_INT

4146

UV MOD16 V3 ENG

APOGEE_INT

4147

UV MOD17 V3 ENG

APOGEE_INT

4148

UV MOD18 V3 ENG

APOGEE_INT

4150

MS 20,30,50 STD

APOGEE_INT

4151

MS 20,30,50 HR

APOGEE_INT

4152

MS 20,30,50 HP

APOGEE_INT

4153

MS 70,90 STD

APOGEE_INT

4160

RTU S100 V4 DAC

APOGEE_INT

4161

RTU S100 V4 SCC

APOGEE_INT

4162

RTU S200 V4 DAC

APOGEE_INT

4163

RTU S200 V4 SCC

APOGEE_INT

4180

DAC

APOGEE_INT

4181

SCC

APOGEE_INT

4300

BTEC 2510

APOGEE_INT

4301

BTEC 2511

APOGEE_INT

4302

BTEC 2512

APOGEE_INT

4303

BTEC 2513

APOGEE_INT

4304

BTEC 2514

APOGEE_INT

4305

BTEC 2515

APOGEE_INT

4306

BTEC 2516

APOGEE_INT

4307

BTEC 2517

APOGEE_INT

4308

BTEC 2587

APOGEE_INT

4310

BTEC 2573

APOGEE_INT

4311

BTEC 2574

APOGEE_INT

4312

BTEC 2590

APOGEE_INT

4313

BUV 2575

APOGEE_INT

4314

BUV 2576

APOGEE_INT

4315

BUV 2577

APOGEE_INT

4316

BUV 2578

APOGEE_INT

4317

BUV 2579

APOGEE_INT

4318

BUV 2595

APOGEE_INT

4320

BTEC 2540

APOGEE_INT

4321

BTEC 2541

APOGEE_INT

4322

BTEC 2550

APOGEE_INT

4323

BTEC 2551

APOGEE_INT

4324

BTEC 2552

APOGEE_INT

4325

BTEC 2553

APOGEE_INT

4326

BTEC 2554

APOGEE_INT

4327

BTEC 2591

APOGEE_INT

4340

BTEC 2510

APOGEE_INT

4341

BTEC 2511

APOGEE_INT

4342

BTEC 2512

APOGEE_INT

4343

BTEC 2513

APOGEE_INT

4344

BTEC 2514

APOGEE_INT

4345

BTEC 2515

APOGEE_INT

4346

BTEC 2516

APOGEE_INT

4347

BTEC 2517

APOGEE_INT

4348

BTEC 2587

APOGEE_INT

4349

BTEC 2540

APOGEE_INT

4350

BTEC 2541

APOGEE_INT

4351

BTEC 2550

APOGEE_INT

4352

BTEC 2551

APOGEE_INT

4353

BTEC 2552

APOGEE_INT

4354

BTEC 2553

APOGEE_INT

4355

BTEC 2554

APOGEE_INT

4356

BTEC 2591

APOGEE_INT

4357

BTEC 2573

APOGEE_INT

4358

BTEC 2574

APOGEE_INT

4359

BTEC 2590

APOGEE_INT

4500

MB DIAG

APOGEE_INT

4501

SQD PM600

APOGEE_INT

4502

SQD BCM42

APOGEE_INT

4503

SQD CM3000

APOGEE_INT

4504

SQD G3 2BUS

APOGEE_INT

4505

SQD G3 4BUS

APOGEE_INT

4506

SQD G3 6BUS

APOGEE_INT

4507

SQD G3 8BUS

APOGEE_INT

4508

SQD MCM8364

APOGEE_INT

4509

SQD ALTIVAR58

APOGEE_INT

4510

SQDL PM600BASIC

APOGEE_INT

4511

SQDL PM600MIN

APOGEE_INT

4512

SQDL PM600MAX

APOGEE_INT

4513

SQDL PM600ENGY

APOGEE_INT

4514

SQDL BCM42BASIC

APOGEE_INT

4515

SQDL BCM42BRKSZ

APOGEE_INT

4516

SQDL BCM42THRSH

APOGEE_INT

4517

SQDL BCM42TMDLY

APOGEE_INT

4518

SQDL CM3000RT1

APOGEE_INT

4519

SQDL CM3000RT2

APOGEE_INT

4520

SQDL CM3000PWRQ

APOGEE_INT

4521

SQDL CM3000MIN

APOGEE_INT

4522

SQDL CM3000MAX

APOGEE_INT

4523

SQDL CM3000ENGY

APOGEE_INT

4524

SQDL G3GRPIP1

APOGEE_INT

4525

SQDL G3GRPIP2

APOGEE_INT

4526

SQDL G3BRKCTR

APOGEE_INT

4529

PM800

APOGEE_INT

4540

SEA PM93XX

APOGEE_INT

4541

SEA PM9700

APOGEE_INT

4542

SEA PM9500

APOGEE_INT

4543

SEA PM9200

APOGEE_INT

4544

SEA PM4700

APOGEE_INT

4545

SEA PM4720

APOGEE_INT

4546

SEA PM4300

APOGEE_INT

4547

SEA STATIC TRIP

APOGEE_INT

4548

SEA SAMMS

APOGEE_INT

4549

SEA SB TRIP

APOGEE_INT

4550

SEA LCP Panel

APOGEE_INT

4551

SEA LCP Global

APOGEE_INT

4553

SEA WL Breaker

APOGEE_INT

4559

SEA DTU Command

APOGEE_INT

4591

VACON VFD

APOGEE_INT

4592

HUNTAIR Standard

APOGEE_INT

4621

YT STD V2

APOGEE_INT

4622

YT SSS V2

APOGEE_INT

4623

YT VSD V2

APOGEE_INT

4624

YK STD V2

APOGEE_INT

4625

YK SSS V2

APOGEE_INT

4626

YK VSD V2

APOGEE_INT

4627

YCAS MSTR V2

APOGEE_INT

4629

YCWS V2

APOGEE_INT

4630

YCAL 2050

APOGEE_INT

4631

YCAL TEMP

APOGEE_INT

4632

YCAL SUCT

APOGEE_INT

4633

YR STD

APOGEE_INT

4634

YR SSS

APOGEE_INT

4635

YS STD

APOGEE_INT

4636

YS SSS

APOGEE_INT

4640

AZL52 Hot Water

APOGEE_INT

4641

AZL52 Steam

APOGEE_INT

4642

AZL51 Hot Water

APOGEE_INT

4643

AZL51 Steam

APOGEE_INT

4644

RWF40

APOGEE_INT

4650

CLIMATIC 50

APOGEE_INT

4990

Modbus Slave

APOGEE_INT

5120

19XL Chiller Controller

APOGEE_INT

5121

19EX Chiller Controller

APOGEE_INT

5122

19XR Chiller Controller

APOGEE_INT

5123

23XL Chiller Controller

APOGEE_INT

5124

3200MP Single Chiller Controller

APOGEE_INT

5125

3200MP Dual Chiller Controller

APOGEE_INT

5126

19XR-2 Chiller Controller, Part 1

APOGEE_INT

5127

19XR-2 Chiller Controller, Part 2

APOGEE_INT

5128

CHILLERVISOR System Manager II (CSM II)

APOGEE_INT

5129

CHILLERVISOR System Manager III (CSM III)

APOGEE_INT

5130

30GT Chiller Controller

APOGEE_INT

5131

30GN Chiller Controller

APOGEE_INT

5132

30GN Maintenance

APOGEE_INT

5133

30GX/HX Chiller Controller, Part 1

APOGEE_INT

5134

30GX/HX Chiller Controller, Part 2

APOGEE_INT

5135

RTU 48/50 - EK, EJ, EW, EY

APOGEE_INT

5136

RTU 48/50 - NB, NP, Part 1

APOGEE_INT

5137

RTU 48/50 - NB, NP, Part 2

APOGEE_INT

5138

16JT Absorption Chiller Controller

APOGEE_INT

5139

17EX Centrifugal Chiller Controller

APOGEE_INT

5320

VVT - Monitor Thermostat (TM01)

APOGEE_INT

5321

VVT - Monitor Controller (VM32)

APOGEE_INT

5322

VVT - Zone Controller - Pressure Dependent (ZC01)

APOGEE_INT

5323

VVT - Zone Controller - Pressure Independent (ZCPI)

APOGEE_INT

5324

VVT - Bypass Controller (BC00)

APOGEE_INT

5336

48/50 EJ/EK/EW/EY Rooftop Unit

APOGEE_INT

5337

Premier Link Controller

APOGEE_INT

5338

48/50A Rooftop Unit 1

APOGEE_INT

5339

48/50A Rooftop Unit 2

APOGEE_INT

5470

Diagnostic

APOGEE_INT

5471

DEVICESONLY

APOGEE_INT

5472

DEV Components

APOGEE_INT

5473

SUBMOD Devices

APOGEE_INT

5474

PSEUDOPOINTS

APOGEE_INT

5475

XLS SUB 1 50

APOGEE_INT

5476

XLSSUB 51 99

APOGEE_INT

5600

N2 Diagnostics

APOGEE_INT

5601

VAV Controller Test Application

APOGEE_INT

5602

UNT Controller Test Application

APOGEE_INT

5603

AHU Controller Test Application

APOGEE_INT

5604

DX9100 Controller Test Application

APOGEE_INT

5607

BIG MOMMA Application

APOGEE_INT

5641

Generic Input/Output (Point Multiplexer)

APOGEE_INT

5642

Generic Input/Output (Point Multiplexer)

APOGEE_INT

5650

JCI UNT GEN RTU

APOGEE_INT

5700

Diagnostic Application

APOGEE_INT

5701

AHU 100% OA Single Path (Constant DA Temperature)

APOGEE_INT

5702

AHU MA Single Path (Room Control)

APOGEE_INT

5703

AHU MA Single Path (Constant DA Temperature)

APOGEE_INT

5704

JCI AHU Controller Application

APOGEE_INT

5705

JCI AHU Controller Application

APOGEE_INT

5706

JCI AHU Controller Application

APOGEE_INT

5707

JCI AHU Controller Application

APOGEE_INT

5708

JCI AHU Controller Application

APOGEE_INT

5709

JCI AHU Controller Application

APOGEE_INT

5710

JCI AHU Controller Application

APOGEE_INT

5712

Diagnostics

APOGEE_INT

5713

FLO2 BLOCK

APOGEE_INT

5714

PEM1 BLOCK

APOGEE_INT

5715

MNFLO BLOCK

APOGEE_INT

5716

MN HP BLOCK

APOGEE_INT

5717

ZONE2 BLOCK

APOGEE_INT

5718

SGCM BLOCK

APOGEE_INT

5719

RLCM BLOCK

APOGEE_INT

5751

DX9100 Controller Application

APOGEE_INT

5752

DX9100 Controller Application

APOGEE_INT

5753

DX9100 Controller Application

APOGEE_INT

5754

DX9100 Controller Application

APOGEE_INT

5800

Data Air DAPII

APOGEE_INT

5801

Bell & Gossett Technologic 500 Speed Drive

APOGEE_INT

5802

B & G Slave Controller for Technologic 500

APOGEE_INT

5810

Square D Series 600 Power meter - Basic

APOGEE_INT

5811

Square D Series 600 Power meter - Minimum Values

APOGEE_INT

5812

Square D Series 600 Power meter - Maximum Values

APOGEE_INT

5813

Square D Series 600 Power meter - Energy and Demand Values

APOGEE_INT

5814

Square D BCM42 Branch Current Monitor - Basic

APOGEE_INT

5815

Square D BCM42 Branch Current Monitor - Breaker Size Configuration

APOGEE_INT

5816

Square D BCM42 Branch Current Monitor - Threshold Configuration

APOGEE_INT

5817

Square D BCM42 Branch Current Monitor - Time Delay Configuration

APOGEE_INT

5818

Square D Circuit Monitor CM3000 and CM4000 - 100ms Real Time

APOGEE_INT

5819

Square D Circuit Monitor CM3000 and CM4000 - 1s Real Time

APOGEE_INT

5820

Square D Circuit Monitor CM3000 and CM4000 - Power Quality

APOGEE_INT

5821

Square D Circuit Monitor CM3000 and CM4000 - Minimum Metered Values

APOGEE_INT

5822

Square D Circuit Monitor CM3000 and CM4000 - Maximum Metered Values

APOGEE_INT

5823

Square D Circuit Monitor CM3000 and CM4000 - Energy

APOGEE_INT

5824

Square D G3 Lighting Control Panel - Group Input Control 1

APOGEE_INT

5825

Square D G3 Lighting Control Panel - Group Input Control 2

APOGEE_INT

5826

Square D G3 Lighting Control Panel - Breaker Control and Monitoring

APOGEE_INT

5840

Diagnostic

APOGEE_INT

5841

Steam Heating

APOGEE_INT

5842

Hot Water Heating

APOGEE_INT

5843

Hot Water Heating Rst

APOGEE_INT

5850

YEP Diagnostic

APOGEE_INT

5851

A1 MASTER

APOGEE_INT

5852

A3 SLAVE

APOGEE_INT

5853

C1 MASTER

APOGEE_INT

5854

C3 SLAVE

APOGEE_INT

5855

LS

APOGEE_INT

5856

RT

APOGEE_INT

5857

YI

APOGEE_INT

5858

YK

APOGEE_INT

5859

YP

APOGEE_INT

5860

YS

APOGEE_INT

5861

YT

APOGEE_INT

5862

CURBMASTER AHU

APOGEE_INT

5863

CURMASTER YCU

APOGEE_INT

5864

YG

APOGEE_INT

5910

SYSTEM

APOGEE_INT

5919

Diagnostic

APOGEE_INT

5920

SINGLE ROOM

APOGEE_INT

6000

Smart 1 Pressure Independent Cooling Only

APOGEE_INT

6001

Smart 1 Pressure Independent Fan Powered

APOGEE_INT

6002

Smart 1 Pressure Independent with Reheat

APOGEE_INT

6003

Smart 1 Pressure Independent Dual Duct

APOGEE_INT

6010

Smart 1 Pressure Dependent Cooling Only

APOGEE_INT

6011

Smart 1 Pressure Dependent Fan Powered

APOGEE_INT

6012

Smart 1 Pressure Dependent with Reheat

APOGEE_INT

6013

Smart 1 Pressure Dependent Dual Duct

APOGEE_INT

6014

Smart 1 Pressure Dependent Fan Powered

APOGEE_INT

6020

Smart 1 Water Source Heat Pump

APOGEE_INT

6021

Smart 1 Interior Zone Air to Air Heat Pump

APOGEE_INT

6022

Smart 1 Exterior Zone Air to Air Heat Pump

APOGEE_INT

6030

Smart 1 2–pipe Changeover Fan Coil Units

APOGEE_INT

6032

Smart 1 2–pipe Cooling only Fan Coil Units with Modulating Valves and Outside Air Damper

APOGEE_INT

6033

Smart 1 4–pipe Fan Coil Unit with Modulating Valves and Outside Air Damper

APOGEE_INT

6040

SMKI Interface

APOGEE_INT

6050

Smart II VAV Generic

APOGEE_INT

6051

Smart II VAV Cooling Only Box

APOGEE_INT

6052

Smart II VAV Dual Duct Box

APOGEE_INT

6053

Smart II VAV Series Fan Powered VAV Box with Modulating Heat Valve

APOGEE_INT

6054

Smart II VAV Parallel Fan Powered VAV Box with Modulating Heating Valve

APOGEE_INT

6055

Smart II VAV Box with Modulating Heating Valve

APOGEE_INT

6056

Smart II VAV Box with Digital Heating Valve

APOGEE_INT

6057

Smart II VAV Series Fan Powered VAV Box with Digital Heat

APOGEE_INT

6058

Smart II VAV Parallel Fan Powered VAV Box with Digital Heat

APOGEE_INT

6060

SMVU VAV Box Generic

APOGEE_INT

6061

SMVU VAV Cooling Only Box

APOGEE_INT

6062

SMVU VAV Series Fan Powered VAV Box with Modulating Heating Valve

APOGEE_INT

6063

SMVU VAV Parallel Fan Powered VAV Box with Modulating Heating Valve

APOGEE_INT

6064

SMVU VAV Box with Modulating Heating Valve

APOGEE_INT

6065

SMVU VAV Box with Digital Heating Valve

APOGEE_INT

6066

SMVU VAV Series Fan Powered VAV Box with Digital Heat

APOGEE_INT

6067

SMVU VAV Parallel Fan Powered VAV Box with Digital Heat

APOGEE_INT

6070

Smart II Heatpump Generic

APOGEE_INT

6071

Smart II Heatpump Single Air Cooled

APOGEE_INT

6072

Smart II Heatpump Single Water Cooled

APOGEE_INT

6073

Smart II Heatpump Multi–stage Air Cooled

APOGEE_INT

6074

Smart II Heatpump Multi–stage Water Cooled

APOGEE_INT

6080

Smart II Fan Coil Unit Generic

APOGEE_INT

6081

Smart II Fan Coil Unit Cooling or Heating

APOGEE_INT

6082

Smart II Fan Coil Unit with Modulating Cooling

APOGEE_INT

6083

Smart II Fan Coil Unit with Changeover Input

APOGEE_INT

6084

Smart II Fan Coil Unit with Changeover Relay

APOGEE_INT

6085

Smart II Fan Coil Unit with Digital Cooling

APOGEE_INT

6090

Smart II Multiplexer Generic

APOGEE_INT

6095

Smart II DDC Controller

APOGEE_INT

6511

BACnet PTEC Unit Conditioner Heating and Cooling with Multi-Speed Fan, On/Off Switch and Occupancy Sensor

APOGEE_PTEC

6520

VAV Cooling Only

APOGEE_PTEC

6521

VAV Cooling or Heating

APOGEE_PTEC

6522

VAV with Electric Reheat

APOGEE_PTEC

6523

VAV with Hot Water Reheat

APOGEE_PTEC

6524

VAV Series Fan Powered with Electric Reheat

APOGEE_PTEC

6525

VAV Series Fan Powered with Hot Water Reheat

APOGEE_PTEC

6526

VAV Parallel Fan Powered with Electric Reheat

APOGEE_PTEC

6527

VAV Parallel Fan Powered with Hot Water Reheat

APOGEE_PTEC

6540

VAV Pressure Depend Cooling or Heating

APOGEE_PTEC

6541

VAV Pressure Depend with 1 or 2 Valve Hot water Reheat

APOGEE_PTEC

6550

Fan Coil Unit 2-pipe Cooling/Heating with optional Heating Valve

APOGEE_PTEC

6551

Fan Coil Unit Cooling and Heating

APOGEE_PTEC

6552

Fan Coil Unit 2-stage Cooling and Electric Reheat

APOGEE_PTEC

6553

Fan Coil Unit 2-stage Cooling and HW Reheat

APOGEE_PTEC

6554

Fan Coil Unit Cooling and Electric Heat

APOGEE_PTEC

6557

VAV VSD Series Fan and 3-stage Electric Heat

APOGEE_PTEC

6560

Constant Volume Cooling Only

APOGEE_PTEC

6562

Constant Volume with Elect. Reheat

APOGEE_PTEC

6563

Constant Volume with Hot Water Reheat

APOGEE_PTEC

6565

BACnet PTEC Dual Duct 2 AVS

APOGEE_PTEC

6566

BACnet PTEC Dual Duct 2 AVS

APOGEE_PTEC

6567

DD VAV 2 Inlet Sensors with optional Reheat

APOGEE_PTEC

6568

BACnet PTEC Dual Duct 2 AVS

APOGEE_PTEC

6569

BACnet PTEC Dual Duct 2 AVS

APOGEE_PTEC

6573

BCNT HP Multi–Compressor Mixed Air Reverse Valve Control

APOGEE_PTEC

6574

BCNT HP HtgClg with Mixed Air and Internal Reverse Valve

APOGEE_PTEC

6575

BCNT UV Heating CW Cooling ASHRAE Cycle I, II

APOGEE_PTEC

6576

BCNT UV Heating CW Cooling ASHRAE Cycle III

APOGEE_PTEC

6577

BCNT UV Heating DX Cooling ASHRAE Cycle I, II

APOGEE_PTEC

6578

BCNT UV Heating DX Cooling ASHRAE Cycle III

APOGEE_PTEC

6579

BCNT UV Heating Cooling NESBITT Cycle W

APOGEE_PTEC

6587

VAV Terminal Box Controller - Slave Mode

APOGEE_PTEC

6590

BACnet Heat Pump - Slave Mode

APOGEE_PTEC

6591

Fan Coil Unit Conditioner - Slave Mode

APOGEE_PTEC

6593

DD 2 AVS - Slave Mode

APOGEE_PTEC

6595

BACnet Unit Vent - Slave Mode

APOGEE_PTEC

6596

TEC with Expanded Point I/O

APOGEE_PTEC

6599

VAV VSD Series Fan - Slave Mode

APOGEE_PTEC

6600

VAV Cooling Only

APOGEE_PTEC

6601

VAV Cooling or Heating

APOGEE_PTEC

6602

VAV with Electric Reheat

APOGEE_PTEC

6603

VAV with Hot Water Reheat

APOGEE_PTEC

6604

VAV Series Fan Powered with Electric Reheat

APOGEE_PTEC

6605

VAV Series Fan Powered with Hot Water Reheat

APOGEE_PTEC

6606

VAV Parallel Fan Powered with Electric Reheat

APOGEE_PTEC

6607

VAV Parallel Fan Powered with Hot Water Reheat

APOGEE_PTEC

6608

BCNT VAV DCV (CO2) Chill Beam

APOGEE_PTEC

6611

FanCoil Heat and Cool Multi–Speed Fan OCC Sensor

APOGEE_PTEC

6620

VAV Cooling Only

APOGEE_PTEC

6621

VAV Cooling or Heating

APOGEE_PTEC

6622

VAV with Electric Reheat

APOGEE_PTEC

6623

VAV with Hot Water Reheat

APOGEE_PTEC

6624

VAV Series Fan Powered with Electric Reheat

APOGEE_PTEC

6625

VAV Series Fan Powered with Hot Water Reheat

APOGEE_PTEC

6626

VAV Parallel Fan Powered with Electric Reheat

APOGEE_PTEC

6627

VAV Parallel Fan Powered with Hot Water Reheat

APOGEE_PTEC

6630

VAV Cooling Only

APOGEE_ATEC?

6631

VAV Cooling or Heating

APOGEE_ATEC

6632

VAV with Electric Reheat

APOGEE_ATEC

6633

VAV with Hot Water Reheat

APOGEE_ATEC

6634

VAV Series Fan Powered with Electric Reheat

APOGEE_ATEC

6635

VAV Series Fan Powered with Hot Water Reheat

APOGEE_ATEC

6636

VAV Parallel Fan Powered with Electric Reheat

APOGEE_ATEC

6637

VAV Parallel Fan Powered with Hot Water Reheat

APOGEE_ATEC

6640

VAV Pressure Dependent Cooling or Heating

APOGEE_PTEC

6641

VAV Pressure Dependent with 1 or 2 Valve Hot Water Reheat

APOGEE_PTEC

6642

VAV Pressure Dependent Cooling or Heating

APOGEE_PTEC

6643

VAV Pressure Dependent with 1 or 2 Valve Hot Water Reheat

APOGEE_PTEC

6644

Fan Coil Unit 2-pipe Cool/Heat with optional Heating Valve

APOGEE_PTEC

6645

Fan Coil Unit Cooling and Heating

APOGEE_PTEC

6646

Fan Coil Unit 2-stage Cooling and Electric Reheat

APOGEE_PTEC

6647

Fan Coil Unit 2-stage Cooling and Hot Water Reheat

APOGEE_PTEC

6648

Fan Coil Unit Cooling and Electric Heat

APOGEE_PTEC

6650

Fan Coil Unit 2-pipe Cool/Heat with optional Heating Valve

APOGEE_PTEC

6651

Fan Coil Unit Cooling and Heating

APOGEE_PTEC

6652

Fan Coil Unit 2-stage Cooling and Electric Reheat

APOGEE_PTEC

6653

Fan Coil Unit 2-stage Cooling and Hot Water Reheat

APOGEE_PTEC

6654

Fan Coil Unit Cooling and Electric Heat

APOGEE_PTEC

6657

VAV with 0-10V Series Fan and 3-stage Electric Reheat

APOGEE_PTEC

6658

BCNT VAV DCV (CO2) and Chilled Beam

APOGEE_PTEC

6659

VAV with DCV (CO2) and Chilled Beam

APOGEE_PTEC

6660

Constant Volume Cooling Only

APOGEE_PTEC

6662

Constant Volume with Electric Reheat

APOGEE_PTEC

6663

Constant Volume with Hot Water Reheat

APOGEE_PTEC

6665

Dual Duct Two Inlet Sensors with Optional Reheat

APOGEE_PTEC

6666

Dual Duct One Inlet One Outlet with Optional Reheat

APOGEE_PTEC

6667

Dual Duct VAV - Two Inlet with Optional Reheat

APOGEE_PTEC

6668

Dual Duct VAV-One Inlet and One Outlet with Reheat

APOGEE_PTEC

6669

Dual Duct VAV with Changeover

APOGEE_PTEC

6673

Heat Pump Multi-Comp with Mixed Air and Reversing Valve

APOGEE_PTEC

6674

Heat Pump Multi-Comp Heat and Cool with Mixed Air

APOGEE_PTEC

6675

Unit Vent 0-10V Heating/Cooling Cycles I

APOGEE_PTEC

6676

Unit Vent 0-10V Heating/Cooling Cycle III

APOGEE_PTEC

6677

Unit Vent 0-10V Heating/DX Cooling Cycles I

APOGEE_PTEC

6678

Unit Vent 0-10V Heating/DX Cooling Cycle III

APOGEE_PTEC

6679

Unit Vent 0-10V Heating/Cooling or DX Cycle W

APOGEE_PTEC

6680

VAV with CO2 Monitor and AOV or Floating Heat

APOGEE_PTEC

6681

VAV with CO2 Monitor Series Fan and AOV or Float Heat

APOGEE_PTEC

6682

VAV with CO2 Monitor Parallel Fan and AOV or Float Heat

APOGEE_PTEC

6684

VAV Terminal Box Controller – Slave Mode

APOGEE_PTEC

6687

VAV Terminal Box Controller - Slave Mode

APOGEE_PTEC

6688

VAV Terminal Box Controller - Slave Mode

APOGEE_PTEC

6689

Fan Coil Unit Conditioner - Slave Mode

APOGEE_PTEC

6690

Heat Pump - Slave Mode

APOGEE_PTEC

6691

Fan Coil Unit Conditioner - Slave Mode

APOGEE_PTEC

6692

VAV with CO2 - Slave Mode

APOGEE_PTEC

6693

Dual Duct - Slave Mode

APOGEE_PTEC

6694

Constant Volume - Slave Mode

APOGEE_PTEC

6695

Unit Vent 0-10v - Slave Mode

APOGEE_PTEC

6696

TEC with Expanded Point I/O

APOGEE_PTEC

6697

FanCoil – Slave Mode

APOGEE_PTEC

6698

VAV with CO2 Monitor – Slave Mode

APOGEE_PTEC

6699

VAV – Slave Mode

APOGEE_PTEC

6700

Fume Hood Controller – Slave Mode

APOGEE_LABS

6720

LRC VAV Rom Pressure with Hot Water Relative Humidity and Two Venturi Valves

APOGEE_LABS

6721

VAV Room Pressure with Hot Water Reheat — One Exhaust

APOGEE_PTEC

6722

LCM-OAVS Venturi Slow RTS

APOGEE_LABS

6723

LCM-OAVS Damper Slow RTS

APOGEE_LABS

6724

LCM-OAVS Damper/Venturi Slow RTS

APOGEE_LABS

6726

LRC VAV with Hot Water Relative Humidity, BTU Compensation and Two Venturi Valves

APOGEE_LABS

6727

VAV Room Pressure with BTU Comp Hot Water Relative Humidity and Fast Actuation

APOGEE_PTEC

6728

LCM-OAVS Venturi Slow BTU

APOGEE_LABS

6729

LCM-OAVS Damper Slow BTU

APOGEE_LABS

6730

LCM-OAVS Damper/Venturi Slow BTU

APOGEE_LABS

6731

Pressurization Control by Differential Flow Reset

APOGEE_CUSTOM

6736

RPC Electronic VAV with Hot Water Reheat and Humidity Control

APOGEE_LABS

6738

RPC Electronic CAV with Hot Water Reheat and Humidity Control

APOGEE_LABS

6740

Fume Hood Controller - 2–position

APOGEE_LABS

6741

Fume Hood Controller – VAV Damper

APOGEE_LABS

6742

Fume Hood Controller - VAV Venturi

APOGEE_LABS

6750

LRC VAV Rom Pressure with Hot Water Relative Humidity and Two Venturi Valves NEW

APOGEE_LABS

6751

VAV Room Pressure with Hot Water Reheat — One Exhaust NEW

VAV Room Pressurization with Hot Water Reheat - One Exhaust, One Supply

APOGEE_LABS

6752

LCM-OAVS Venturi Slow RTS NEW

APOGEE_LABS

6753

LCM-OAVS Damper Slow RTS NEW

APOGEE_LABS

6754

LCM-OAVS Damper/Venturi Slow RTS NEW

APOGEE_LABS

6756

LRC VAV with Hot Water Relative Humidity, BTU Compensation and Two Venturi Valves NEW

APOGEE_LABS

6757

VAV Room Pressure with BTU Comp Hot Water Relative Humidity and Fast Actuation NEW

APOGEE_LABS

6758

LCM-OAVS Venturi Slow BTU NEW

APOGEE_LABS

6759

LCM-OAVS Damper Slow BTU NEW

APOGEE_LABS

6760

LCM-OAVS Damper/Venturi Slow BTU NEW

APOGEE_LABS

6761

Pressurization Control by Differential Flow Reset NEW

APOGEE_LABS

6763

Pressurized Room Controller (PRC)

0APOGEE_LABS

6765

Pressurized Room Controller (PRC) – Slave Mode

APOGEE_LABS

6773

Pressurized Room Controller (PRC) NEW

APOGEE_LABS

6775

Pressurized Room Controller (PRC) - Slave Mode NEW

APOGEE_LABS

6792

Slave Mode NEW

APOGEE_LABS

8020

VAV Cooling

APOGEE_LON

8022

VAV Electric Reheat

APOGEE_LON

8023

VAV Hot Water

APOGEE_LON

8024

VAV Electric Reheat Series Fan

APOGEE_LON

8025

VAV Hot Water Reheat Series Fan

APOGEE_LON

8026

VAV Electric Reheat Parallel Fan

APOGEE_LON

8027

VAV Hot Water Reheat Parallel Fan

APOGEE_LON

8032

CV Electric Reheat

APOGEE_LON

8033

CV Hot Water Reheat

APOGEE_LON

8050

FC CW 2–pipe Hot Water Heat

APOGEE_LON

8051

FC CW 4–pipe

APOGEE_LON

8052

FC DX Electric Heat

APOGEE_LON

8053

FC DX Hot Water Heat

APOGEE_LON

8054

FC CW 2–pipe Electric Heat

APOGEE_LON

8071

HP REV Valve Electric Heat

APOGEE_LON

8072

HP Electric Heat

APOGEE_LON

8073

HP 2-stage REV Valve Electric Heat

APOGEE_LON

8074

HP 2-stage Electric Heat

APOGEE_LON

8081

UV CW 4-pipe

APOGEE_LON

8084

UV DX Hot Water Reheat

APOGEE_LON

8086

UV DX Electric Reheat

APOGEE_LON

8088

UV CW 2-pipe

APOGEE_LON

8089

UV FACE BYPASS 2-pipe, 4-pipe

APOGEE_LON

8101

VAV Electric Reheat Variable Speed Fan

APOGEE_CUSTOM

8102

VAV HW Reheat Variable Speed Fan

APOGEE_CUSTOM

14020

VAV Cooling Only

APOGEE_DXR

14022

VAV with 2-stage Electric Heat

APOGEE_DXR

14023

VAV Hot Water

APOGEE_DXR

14123

VAV Hot Water with Supply Temperature Control

APOGEE_DXR

14024

VAV Series Fan Powered Box with 2-stage Electric Heat

APOGEE_DXR

14025

VAV Series Fan Powered Box with Hot Water

APOGEE_DXR

14125

VAV Series Fan Powered Box with Hot Water and Supply Temperature Control

APOGEE_DXR

14026

VAV Parallel Fan Powered Box with 2-stage Electric Heat

APOGEE_DXR

14027

VAV Parallel Fan Powered Box with Hot Water

APOGEE_DXR

14127

VAV Parallel Fan Powered Box with Hot Water and Supply Temperature Control

APOGEE_DXR

14050

Fan Coil 2-pipe Heating/Cooling and Hot Water Coil

APOGEE_DXR

14051

Fan Coil 4-pipe with Chilled Water and Hot Water

APOGEE_DXR

14052

Fan Coil with 2-stage DX Cool and 2-stage Electric Heat

APOGEE_DXR

14054

Fan Coil with Chilled Water and 2-stage Electric Heat

APOGEE_DXR

14058

Chilled Beam Passive Heating and Cooling and Hot Water Radiator

APOGEE_DXR

14064

Dual Duct Variable Volume with Dedicated Ventilation Duct, Two Inlet Sensors, DCV and Hot Water Heat with Supply Temp Control NEW

APOGEE_DXR

14069

Dual Duct Variable Volume with Two Inlet Sensors and Hot Water Radiator New

APOGEE_DXR

14081

Fan Coil Unit Vent with Chilled Water and Hot Water and OA Damper

APOGEE_DXR

14083

Fan Coil Unit Vent with Chilled Water and 2-stage Electric Heat and OA Damper

APOGEE_DXR

14070

HP Var Spd with RV, Vari-Spd Fan, 2-Stg Elec Heat and 1-Sg Elec Rad and OAD

APOGEE_DXR

14071

HP Multi-Stg with RV Multi-Spd Fan 2-Stg Elec Heat and HW Rad and OAD

APOGEE_DXR

14072

HP Multi-Stg Gnd Src with Int RV and HG Rht Vari-Spd Fan 1-Stg Elec Heat HW Rad and OAD

APOGEE_DXR

14084

Fan Coil Unit Vent with 2-stage DX Cool and HW and OA Damper

APOGEE_DXR

14158

Chilled Beam Active Heating and Cooling with VAV and Hot Water Radiator

APOGEE_DXR

14169

Dual Duct Variable Volume with Two Inlet Sensors, DCV and Hot Water Radiator NEW

APOGEE_DXR

14171

HP Multi-Stg with RV and H Gas Rht Multi-Spd Fan 1-Stg Elec Heat and HW Rad and OAD

APOGEE_DXR

14184

Fan Coil Unit Vent with 2-stage DX Cool and 2-stage Electric Heat and OA Damper

APOGEE_DXR

14258

Chilled Beam Active Heating and Cooling with VAV and Electric 1-stage Radiator

APOGEE_DXR

14269

Dual Duct Variable Volume with Two Inlet Sensors, Chilled Ceiling and Hot Water Radiator NEW

APOGEE_DXR

14270

HP 1-Stg with RV 1-Spd Fan 1-Stg Elec Heat and HW Rad and OAD

APOGEE_DXR

14358

Chilled Beam Passive 2-pipe Heating/Cooling and Electric 1-stage Radiator

APOGEE_DXR

14369

Dual Duct Variable Volume with Two Inlet Sensors, Hot Water Heat and 1-Stage Electric Radiator

APOGEE_DXR

14458

Chilled Beam Passive 2-pipe Heating/Cooling and Electric 1-Stage Radiator NEW

APOGEE_DXR

14550

Fan Coil 2-pipe Heating/Cooling and Hot Water Coil

APOGEE_DXR

14551

Fan Coil 4-pipe with Chilled Water and Hot Water

APOGEE_DXR

14552

Fan Coil with 2-stage DX Cool and 2-stage Electric Heat

APOGEE_DXR

14554

Fan Coil with Chilled Water and 2-stage Electric Heat

APOGEE_DXR

14581

Fan Coil Unit Vent with Chilled Water and Hot Water and OA Damper

APOGEE_DXR

14583

Fan Coil Unit Vent with Chilled Water and 2-stage Electric Heat and OA Damper

APOGEE_DXR

14584

Fan Coil Unit Vent with 2-stage DX Cool and HW and OA Damper

APOGEE_DXR

14670

HP 1-Stg with RV 1-Spd Fan 1-Stg Elec Heat and HW Rad and OAD NEW

APOGEE_DXR

14684

Fan Coil Unit Vent with 2-stage DX Cool and 2-stage Electric Heat and OA Damper

APOGEE_DXR

14720

ADXR VAV Cooling Only NEW

APOGEE_DXR

14722

ADXR VAV with 2-Stage Electric Heat NEW

APOGEE_DXR

14723

ADXR VAV Hot Water NEW

APOGEE_DXR

14724

ADXR VAV Series Fan Powered Box with 2-Stage Electric Heat NEW

APOGEE_DXR

14725

ADXR VAV Series Fan Powered Box with Hot Water NEW

APOGEE_DXR

14726

ADXR VAV Parallel Fan Powered Box with 2-Stage Electric Heat NEW

APOGEE_DXR

14727

ADXR VAV Parallel Fan Powered Box with Hot Water NEW

APOGEE_DXR

14820

ADXR VAV Cooling Only – UFAD NEW

APOGEE_DXR

14823

ADXR VAV Hot Water with Supply Temp Control NEW

APOGEE_DXR

14825

ADXR VAV Series Fan Powered Box with Hot Water and Supply Temp Control NEW

APOGEE_DXR

14827

ADXR VAV Parallel Fan Powered Box with Hot Water and Supply Temp Control NEW

APOGEE_DXR

14828

ADXR VAV Parallel Fan Powered Box with Hot Water and Supply Temp Control – UFAD NEW

APOGEE_DXR

14900

RDY2000BN BACnet Thermostat Conventional

APOGEE_BTEC

14901

RDY2000BN BACnet Thermostat Heat Pump

APOGEE_BTEC

16741

Fume Hood Vertical Sash Configuration with Modulating Damper

APOGEE_DXR

16742

Fume Hood Vertical Sash Configuration with Modulating Venturi

APOGEE_DXR

16750

Lab Room VAV Pressurization with Fast-Action Venturi Air Valves and HW Reheat

APOGEE_DXR

16751

Lab Room VAV Pressurization with Fast-Action Dampers and HW Reheat

APOGEE_DXR

16756

Lab Room VAV Pressurization with Fast-Action Venturi Air Valves and HW Reheat – Thermal Power Control

APOGEE_DXR

16773

Lab Room VAV Pressurization with Slow Floating Dampers, HW Reheat, Supply Temp

APOGEE_DXR

16850

Lab Room VAV Pressurization with Fast-Action Venturi Air Valves and HW Reheat

APOGEE_DXR

16851

Lab Room VAV Pressurization with Fast-Action Dampers and HW Reheat

APOGEE_DXR

16856

Lab Room VAV Pressurization with Fast-Action Venturi Air Valves and HW Reheat - Thermal Power Control

APOGEE_DXR

65535

Undefined or failed BACnet FLN Device

APOGEE_MISC

Importing the FLN Libraries
  • System Manager is in Engineering mode.
  1. In System Browser, select Management View > System Settings > Libraries.
  1. Click the Library Configurator tab.
  1. Click the Import button.
  • The Import Libraries dialog box displays.
  1. Select the [GMSProject] > Libraries > Exports folder.
  1. From the list of libraries, select only the FLN libraries you need for your project—those that correspond to your FLN applications.
  1. Click Open.
  1. When asked if you want to import the folder structures for the various libraries, click Yes for individual libraries, or Yes to all for all the libraries you selected.
  • The folder structure is added to the Libraries > BA (HQ) > Room equipment folder.