Adding FLN Application Libraries
During the integration, you are asked to select FLN application libraries. Since there are hundreds of FLN applications, select only those needed for your project. Otherwise, you will hinder system performance. Also, there are FLN libraries for both EN (US Standard) and SI (Metric) environments. Install only those needed for your environment. In other words, install one group or the other, but not both.
The project template BA_NA includes an FLN Application Guide that shows which libraries must be imported for the various TEC application numbers. You can find the guide in the Desigo CC System Browser. Once you have selected Application View and Show Description, select:
Applications > Documents > FLN Application Library Guide
Alternatively, you can click the link at the end of this topic to view the full list of supported applications.
The following table shows a list of library categories, followed by their names in the Import Libraries dialog box.
Library Category | EN | SI |
APOGEE_CUSTOM | BA_Room_TEC_APOGEE_CUSTOM_EN_HQ_1.gms | BA_Room_TEC_APOGEE_CUSTOM_SI_HQ_1.gms |
APOGEE_LABS | BA_Room_TEC_APOGEE_LABS_EN_HQ_1.gms | BA_Room_TEC_APOGEE_LABS_SI_HQ_1.gms |
APOGEE_P1 | BA_Room_TEC_APOGEE_P1_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P1_AI_HQ_1.gms |
APOGEE_P1SEC | BA_Room_TEC_APOGEE_P1SEC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P1SEC_SI_HQ_1.gms |
APOGEE_ATEC | BA_Room_TEC_APOGEE_ATEC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_ATEC_SI_HQ_1.gms |
APOGEE_BTEC | BA_Room_TEC_APOGEE_BTEC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_BTEC_SI_HQ_1.gms |
APOGEE_PTEC | BA_Room_TEC_APOGEE_PTEC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_PTEC_SI_HQ_1.gms |
APOGEE_INT | BA_Room_TEC_APOGEE_INT_EN_HQ_1.gms | BA_Room_TEC_APOGEE_INT_SI_HQ_1.gms |
APOGEE_LON | BA_Room_TEC_APOGEE_LON_EN_HQ_1.gms | BA_Room_TEC_APOGEE_LON_SI_HQ_1.gms |
APOGEE_MISC | BA_Room_TEC_APOGEE_MISC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_MISC_SI_HQ_1.gms |
APOGEE_P2_PTEC | BA_Room_TEC_APOGEE_P2_PTEC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_PTEC_SI_HQ_1.gms |
APOGEE_P2_P1SEC | BA_Room_TEC_APOGEE_P2_P1SEC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_P1SEC_SI_HQ_1.gms |
APOGEE_P2_P1 | BA_Room_TEC_APOGEE_P2__P2_P1_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_ P2_P1_SI_HQ_1.gms |
APOGEE_P2_MISC | BA_Room_TEC_APOGEE_P2__MISC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_ MISC_SI_HQ_1.gms |
APOGEE_P2_LON | BA_Room_TEC_APOGEE_P2__LON_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_ LON_SI_HQ_1.gms |
APOGEE_P2_LABS | BA_Room_TEC_APOGEE_P2__LABS_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_ LABS_SI_HQ_1.gms |
APOGEE_P2_INT1 | BA_Room_TEC_APOGEE_P2__INT1_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_ INT1_SI_HQ_1.gms |
APOGEE_P2_Custom | BA_Room_TEC_APOGEE_P2__Custom_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_ Custom_SI_HQ_1.gms |
APOGEE_P2_BTEC | BA_Room_TEC_APOGEE_P2__BTEC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_ BTEC_SI_HQ_1.gms |
APOGEE_P2_ATEC | BA_Room_TEC_APOGEE_P2__ATEC_EN_HQ_1.gms | BA_Room_TEC_APOGEE_P2_ ATEC_SI_HQ_1.gms |
Use the following table to match your FLN applications to the appropriate TEC library, and then install only the libraries you need for your project. Recent additions are indicated with a NEW next to them.
Appl | Description | Library |
600 | Fume Hood - 9 Horizontal combination Sash with VSD | APOGEE_LABS |
603 | Fume Hood - Single or Multi-vertical Sash with Damper | APOGEE_LABS |
604 | Fume Hood - 603 with VSD output | APOGEE_CUSTOM |
605 | Fume Hood - Horizontal Sash with Damper | APOGEE_LABS |
606 | Fume Hood - 605 with VSD output | APOGEE_CUSTOM |
607 | Fume Hood - Combination Sash with Damper | APOGEE_LABS |
608 | Fume Hood - 607 with VSD output | APOGEE_CUSTOM |
613 | Fume Hood - 4 Vertical across | APOGEE_CUSTOM |
615 | Fume Hood - 5 to 9 Horizontal Sash with Damper | APOGEE_CUSTOM |
617 | Fume Hood - 9 Horizontal Combination Sash with Damper | APOGEE_CUSTOM |
625 | Fume Hood - Cal. Hood, 4 Horizontal Sashes on two sides | APOGEE_CUSTOM |
627 | Fume Hood-10 Horizontal Sashes, flow input/0-10 Vdc output | APOGEE_CUSTOM |
628 | Fume Hood-615 with maximum flow Sash alert, 2 facevel setpoint | APOGEE_CUSTOM |
629 | Fume Hood-605 with a separate Vertical Sash | APOGEE_CUSTOM |
630 | Fume Hood - 2-position Controller | APOGEE_CUSTOM |
631 | Fume Hood- walk-in, no face area in lower sash | APOGEE_CUSTOM |
632 | Fume Hood - Dual combination | APOGEE_CUSTOM |
639 | Fume Hood - 603 with flow input 0-10 Vdc output | APOGEE_CUSTOM |
643 | Fume Hood - 603 with 2 facvel setpoints and sash alert | APOGEE_CUSTOM |
645 | Fume Hood - 605 with 2 facvel setpoints and sash alert | APOGEE_CUSTOM |
647 | Fume Hood - 607 with 2 facvel setpoints and sash alert | APOGEE_CUSTOM |
650 | Constant Volume Fume Hood Monitor - Slave Mode | APOGEE_LABS |
651 | Constant Volume Fume Hood Monitor | APOGEE_LABS |
652 | Fume Hood - 10 combination walk-in with maximum flow | APOGEE_CUSTOM |
658 | Fume Hood - 603 with maximum flow, sash alert, 2 facevel setpoints | APOGEE_CUSTOM |
659 | Fume Hood - 605 with maximum flow, sash alert, 2 facevel setpoints | APOGEE_CUSTOM |
660 | Fume Hood - 607 with maximum flow, sash alert, 2 facevel setpoints | APOGEE_CUSTOM |
701 | DPM - Single Sensor Operation, Healthcare Application | APOGEE_LABS |
702 | DPM - Dual Sensor Operation, Healthcare Application | APOGEE_LABS |
703 | DPM - Single Sensor Operation, Lab Application | APOGEE_LABS |
704 | DPM - Dual Sensor Operation, Lab Application | APOGEE_LABS |
710 | Digital Energy Monitor Ser. 1000, 100A Small CT | APOGEE_LABS |
711 | Digital Energy Monitor Ser. 1000, 300A Small CT | APOGEE_LABS |
712 | Digital Energy Monitor Ser. 1000, 400A Medium CT | APOGEE_LABS |
713 | Digital Energy Monitor Ser. 1000, 800A Medium CT | APOGEE_LABS |
714 | Digital Energy Monitor Ser. 1000, 800A Large CT | APOGEE_LABS |
715 | Digital Energy Monitor Ser. 1000, 1600A Large CT | APOGEE_LABS |
716 | Digital Energy Monitor Ser. 1000, 2400A Large CT | APOGEE_LABS |
717 | Digital Energy Monitor S2000, 100A, Small CT | APOGEE_LABS |
718 | Digital Energy Monitor S2000, 300A, Small CT | APOGEE_LABS |
719 | Digital Energy Monitor S2000, 400A, Medium CT | APOGEE_LABS |
721 | Digital Energy Monitor S2000, 800A, Large CT | APOGEE_LABS |
722 | Digital Energy Monitor S1600, 2400A, Large CT | APOGEE_LABS |
723 | Digital Energy Monitor S2000, 2400A, Large CT | APOGEE_LABS |
790 | DPM - Slave Mode | APOGEE_LABS |
900 | FHC, 8 Horizontal Walk-in - Slave Mode | APOGEE_LABS |
903 | Fume Hood - Single/Multi-Vertical Sash with Damper | APOGEE_LABS |
905 | Fume Hood - Horizontal Sash with Damper | APOGEE_LABS |
907 | Fume Hood - Combination Sash with Damper | APOGEE_LABS |
920 | Fume Hood - 903 with Auto Zero | APOGEE_CUSTOM |
921 | Fume Hood - 905 with Auto Zero | APOGEE_CUSTOM |
922 | Fume Hood - 907 with Auto Zero | APOGEE_CUSTOM |
923 | Fume Hood - 903 with AO2 = Actual Flow | APOGEE_CUSTOM |
924 | Fume Hood - 905 with AO2 = Actual Flow | APOGEE_CUSTOM |
925 | Fume Hood - 907 with AO2 = Actual Flow | APOGEE_CUSTOM |
926 | Fume Hood - 903 for Venturi Air Valve | APOGEE_CUSTOM |
927 | Fume Hood - 905 for Venturi Air Valve | APOGEE_CUSTOM |
928 | Fume Hood - 907 for Venturi Air Valve | APOGEE_CUSTOM |
929 | FHC/8 Horizontal Walk-in, 2 Vertical Heights with FS19 | APOGEE_CUSTOM |
929 | FHC/Damper, 8 Horizontal Walk-in, 2 Vertical Heights | APOGEE_CUSTOM |
930 | FHC/Damper, Dual Combination | APOGEE_LABS |
933 | FHC/Vent, 8 Horizontal Walk-in, 2 Vertical Heights | APOGEE_CUSTOM |
934 | FHC Application 905 with Differential Horizontal Sash Widths | APOGEE_CUSTOM |
935 | FHC Application 907 with Differential Horizontal Sash Widths | APOGEE_CUSTOM |
940 | Constant Volume, 2-Position Fume Hood | APOGEE_LABS |
941 | FHC/Damper, 8 Horizontal Walk-in, 2 Vertical Height/Differential Widths | APOGEE_LABS |
942 | FHC/Vent, 8 Horizontal Walk-in, 2 Vertical Height/Differential Widths | APOGEE_LABS |
2020 | VAV Cooling Only | APOGEE_P1 |
2021 | VAV Cooling or Heating | APOGEE_P1 |
2022 | VAV with Electric Reheat | APOGEE_P1 |
2023 | VAV with Hot Water Reheat | APOGEE_P1 |
2024 | VAV Series Fan Powered with Electric Reheat | APOGEE_P1 |
2025 | VAV Series Fan Powered with Hot Water Reheat | APOGEE_P1 |
2026 | VAV Parallel Fan Powered with Electric Reheat | APOGEE_P1 |
2027 | VAV Parallel Fan Powered with Hot Water Reheat | APOGEE_P1 |
2030 | Constant Volume Cooling Only | APOGEE_P1 |
2032 | Constant Volume with Electric Reheat | APOGEE_P1 |
2033 | Constant Volume with Hot Water Reheat | APOGEE_P1 |
2035 | DD Constant Volume 2 Inlet Damper Acts with optional Reheat | APOGEE_P1 |
2036 | DD Constant Volume 1 Inlet 1 Outlet Damper with optional Reheat | APOGEE_P1 |
2040 | VAV Pressure Dependent Cooling or Heating | APOGEE_P1 |
2041 | VAV Pressure Dependent with 1 or 2 Valve Hot Water Reheat | APOGEE_P1 |
2050 | Fan Coil Unit 2-pipe Cool/Heat with optional Heating Valve | APOGEE_P1 |
2051 | Fan Coil Unit Cooling and Heating | APOGEE_P1 |
2052 | Fan Coil Unit 2-stage Cooling and Electric Reheat | APOGEE_P1 |
2053 | Fan Coil Unit 2-stage Cooling and Hot Water Reheat | APOGEE_P1 |
2054 | Fan Coil Unit Cooling and Electric Heat | APOGEE_P1 |
2064 | DD VAV 2 Position Hot/Cold Damper and Volume Damper with optional Reheat | APOGEE_P1 |
2065 | DD VAV 2 Inlet Damper Actuators with optional Reheat | APOGEE_P1 |
2066 | DD VAV 1 Inlet 1 Outlet Damper Actuator with optional Reheat | APOGEE_P1 |
2070 | Heat Pump 1 Compressor with Reversing Valve Control | APOGEE_P1 |
2071 | Heat Pump 2 Compressor with Reverse Valve Control | APOGEE_P1 |
2072 | Heat Pump Heat/Cool without Reverse Valve Control | APOGEE_P1 |
2090 | Unit Cond. with Pot Control of Damper - Slave Mode | APOGEE_P1 |
2091 | Slave Mode for VAV Application 2026 with modified fan | APOGEE_P1 |
2092 | Constant Volume - Slave Mode with 2" WC | APOGEE_P1 |
2100 | CV Hot Water RH, Humidity Control and Secure Mode | APOGEE_CUSTOM |
2120 | Cooling Only with Secure Mode | APOGEE_P1SEC |
2121 | VAV Cooling or Heating with Secure Mode | APOGEE_P1SEC |
2122 | Electric RH or Baseboard Heat and Secure Mode | APOGEE_P1SEC |
2123 | VAV with Hot Water Reheat and Secure Mode | APOGEE_P1SEC |
2124 | VAV Series Fan and Electric Heat and Secure Mode | APOGEE_P1SEC |
2125 | VAv Series Fan and Hot Water Reheat and Secure Mode | APOGEE_P1SEC |
2126 | VAV Parallel Fan with Electric Heat and Secure Mode | APOGEE_P1SEC |
2127 | VAV Parallel Fan with Hot Water Reheat and Secure Mode | APOGEE_P1SEC |
2130 | Part 11 Constant Volume Cooling Only | APOGEE_P1SEC |
2132 | Part 11 Constant Volume with Electric Reheat | APOGEE_P1SEC |
2133 | Part 11 Constant Volume with Hot Water Reheat | APOGEE_P1SEC |
2140 | Part 11 VAV Pressure Dependent Cooling or Heating | APOGEE_P1SEC |
2141 | Part 11 VAV Pressure Dependent with 1 - 2 Valve Hot Water Reheat | APOGEE_P1SEC |
2150 | Part 11 Fan Coil Unit 2-pipe Cool/Heat Optional Heating Valve | APOGEE_P1SEC |
2151 | Part 11 Fan Coil Unit Cooling and Heating | APOGEE_P1SEC |
2152 | Part 11 Fan Coil Unit 2-stage Cooling and Electric Reheat | APOGEE_P1SEC |
2153 | Part 11 Fan Coil Unit 2-stage Cooling and Hot Water Reheat | APOGEE_P1SEC |
2154 | Part 11 Fan Coil Unit Cooling and Electric Heat | APOGEE_P1SEC |
2188 | Part 11 Fan Coil Unit Conditioner - Slave Mode | APOGEE_P1SEC |
2190 | CV Controller with Secure Mode - Slave Mode | APOGEE_P1SEC |
2191 | VAV with Secure Mode - Slave Mode | APOGEE_P1SEC |
2192 | Part 11 Constant Volume Controller - Slave Mode | APOGEE_P1SEC |
2197 | TEC with Expanded I/O Capability and Secure Mode | APOGEE_CUSTOM |
2215 | RPC Pneumatic CAV with Hot Water Reheat and VAV Switchover | APOGEE_LABS |
2216 | RPC Electronic VAV with Hot Water Reheat | APOGEE_LABS |
2217 | RPC Pneumatic VAV with Hot Water Reheat | APOGEE_LABS |
2218 | RPC Electronic CAV with Hot Water Reheat | APOGEE_LABS |
2219 | RPC Pneumatic CAV with Hot Water Reheat | APOGEE_LABS |
2237 | DD Const Vol 2 Inlet Sensors with optional Reheat | APOGEE_P1 |
2238 | DD Const Vol 1 Inlet 1 Outlet Sensor with optional Reheat | APOGEE_P1 |
2267 | DD VAV 2 Inlet Sensors with optional Reheat | APOGEE_P1 |
2268 | DD VAV 1 Inlet 2 Outlet Sensor with optional Reheat | APOGEE_P1 |
2269 | DD VAV with Hot Duct to second Cold Duct Changeover | APOGEE_P1 |
2273 | Heat Pump Multi-Stage with Reverse Valve Control | APOGEE_P1 |
2274 | Heat Pump Multi-Stage without Reverse Valve Control | APOGEE_P1 |
2276 | Unit Vent Heat Pump with Reverse Valve and Cycles I, II | APOGEE_CUSTOM |
2277 | Unit Vent Heat Pump with Reverse Valve and Cycle III | APOGEE_CUSTOM |
2278 | Unit Vent Heat Pump without Reverse Valve and Cycles I, II | APOGEE_CUSTOM |
2279 | Unit Vent Heat Pump without Reverse Valve and Cycle III | APOGEE_CUSTOM |
2281 | Unit Vent 0-10V Heating/Cooling Cycles I, II | APOGEE_P1 |
2283 | Unit Vent 0-10V Heating/Cooling Cycle III | APOGEE_P1 |
2284 | Unit Vent 0-10V Heating/DX Cycles I, II | APOGEE_P1 |
2286 | Unit Vent 0-10V Heating/DX Cycle III | APOGEE_P1 |
2287 | Unit Vent 0-10V Heating/Cooling/DX Cycle W | APOGEE_P1 |
2290 | Heat Pump Multi-Stage - Slave Mode | APOGEE_P1 |
2293 | Dual Duct VAV with Ventilation - Slave Mode | APOGEE_P1 |
2294 | Lab Press Controller - Slave Mode | APOGEE_LABS |
2295 | CAV Pneumatic with 0-10V Flow - Slave Mode | APOGEE_P1 |
2299 | VAV w/CW 2-position. OA Damper and Static Pressure – Slave Mode | APOGEE_P1 |
2300 | Constant Volume with Hot Water Reheat and Humidity Control | APOGEE_CUSTOM |
2301 | VAV with Hot Water Reheat and Humidity Control | APOGEE_CUSTOM |
2302 | Relative Humidity Control Using Specific Humidity | APOGEE_CUSTOM |
2303 | Relative Humidity Control | APOGEE_CUSTOM |
2304 | VAV with 2-speed Series Fan, Hot Water Valve, Discharge Flow Monitor | APOGEE_CUSTOM |
2305 | VAV with 2-speed Series Fan, Electric Heating, Discharge Flow Monitor | APOGEE_CUSTOM |
2306 | Unit Vent with Relative Humidity Control and Hot Water Heating | APOGEE_CUSTOM |
2307 | Unit Vent with Dew Point Temperature Control and Hot Water Heating | APOGEE_CUSTOM |
2308 | VAV with CHW, Hot Water, Econ Cycle, Static Pressure Control | APOGEE_CUSTOM |
2309 | VAV with CHW, Electric Heat, Econ Cycle, Static Pressure Control | APOGEE_CUSTOM |
2310 | VAV with DX, Electric/RC Heat, Static Pressure Control, Dumpback Damper | APOGEE_CUSTOM |
2311 | CAV with CHW, Hot Water, Econ Cycle, CO2 Sensor | APOGEE_CUSTOM |
2312 | CAV with CHW, Electric Heat, Econ Cycle, CO2 Sensor | APOGEE_CUSTOM |
2313 | CAV with DX, Electric or RC Hot Water, Econ Cycle, CO2 Sensor | APOGEE_CUSTOM |
2314 | Constant Volume Cooling Only with No Damper Calibration | APOGEE_CUSTOM |
2315 | Constant Volume Electric Reheat with No Damper Calibration | APOGEE_CUSTOM |
2316 | RPC Electronic VAV with Hot Water Reheat and No Damper Calibration | APOGEE_CUSTOM |
2317 | Constant Volume Hot Water Reheat with No Damper Calibration | APOGEE_CUSTOM |
2318 | RPC Electronic CAV with Hot Water Reheat and No Damper Calibration | APOGEE_CUSTOM |
2319 | Unit Vent with Relative Humidity Control and Electric Heating | APOGEE_CUSTOM |
2320 | VAV Fan with Flow, Temperature, and Static Pressure Control | APOGEE_CUSTOM |
2321 | VAV Fan with Flow and Temperature Control | APOGEE_CUSTOM |
2322 | RPC Pneumatic CAV with BTU Compensation | APOGEE_CUSTOM |
2323 | Fan Coil with 6-stages of Electric Reheat | APOGEE_CUSTOM |
2324 | Fan Coil with 6-stages of Cooling | APOGEE_CUSTOM |
2326 | Heat Pump 1 Compressor with Reverse Valve and Dehumidification | APOGEE_CUSTOM |
2327 | Unit Vent with 2-DX Cycle III | APOGEE_CUSTOM |
2328 | VAV with Hot Water Reheat and SCR Fan | APOGEE_CUSTOM |
2329 | VAV Series Fan Powered with 2-speed Fan and Electric Reheat | APOGEE_CUSTOM |
2330 | CAV Pneumatic with 0-10V Flow | APOGEE_CUSTOM |
2332 | LRC with BTU Compensation | APOGEE_CUSTOM |
2333 | VAV with Induction Damper | APOGEE_CUSTOM |
2334 | Unit Vent with FBD, Heating and DX Cooling ASHRAE Cycle 1 &2 | APOGEE_CUSTOM |
2335 | VAV with Dehumidification | APOGEE_CUSTOM |
2336 | RPC Electronic VAV with Hot Water Reheat and Humidity Control | APOGEE_CUSTOM |
2337 | VAV with CW, 2-position OA Damper and Static Pressure | APOGEE_CUSTOM |
2338 | RPC Electronic CAV with Hot Water Reheat and Humidity Control | APOGEE_CUSTOM |
2339 | Fan Coil Dual Zone Unit 2-pipe Cool/Heat | APOGEE_CUSTOM |
2341 | Unit Vent Controller with Mixed Air Sequence | APOGEE_CUSTOM |
2342 | Unit Vent with Mixed Air Sequence and DX Cooling | APOGEE_CUSTOM |
2343 | LRC Pneumatic Application 2343 | APOGEE_CUSTOM |
2344 | LRC Pneumatic Application 2344 | APOGEE_CUSTOM |
2345 | LRC Pneumatic Application 2343 | APOGEE_CUSTOM |
2346 | Fan Coil with 3-speed Fan and Dehumidification | APOGEE_CUSTOM |
2347 | Fan Coil 4-Pipe with 3-Speed Fan | APOGEE_CUSTOM |
2348 | Unit Vent Controller with Free Cooling, Night Purge and Dehumidification, 0-10V Output | APOGEE_CUSTOM |
2349 | Unit Vent Controller with Free Cooling, Night Purge and Dehumidification | APOGEE_CUSTOM |
2352 | Unit Vent with Mixed Air and Dehumidification | APOGEE_CUSTOM |
2353 | Unit Vent with Mixed Air and Dehumidification | APOGEE_CUSTOM |
2354 | Unit Vent with Heat and/or CW Cool and Cycles I, II | APOGEE_CUSTOM |
2355 | Unit Vent with Heat and/or CW Cool and Cycle III | APOGEE_CUSTOM |
2356 | Unit Vent w/Heat and DX Cooling and Cycles I, II | APOGEE_CUSTOM |
2357 | Unit Vent with Heat and DX Cooling and Cycle III | APOGEE_CUSTOM |
2358 | Fan Coil 4-pipe with 2–speed Fan | APOGEE_CUSTOM |
2359 | Dual Duct VAV with Ventilation | APOGEE_CUSTOM |
2360 | VAV with CO2 Monitoring - Cooling Only | APOGEE_CUSTOM |
2361 | VAV with CO2 Monitoring - Cooling and Heating | APOGEE_CUSTOM |
2362 | VAV with CO2 Monitoring - Electric Heat or Baseboard Radiation | APOGEE_CUSTOM |
2363 | VAV with CO2 Monitoring - Hot Water Reheat | APOGEE_CUSTOM |
2364 | VAV with CO2 Monitoring - Fan Powered with Electric Reheat | APOGEE_CUSTOM |
2365 | VAV with CO2 Monitoring - Fan Powered with Hot Water Reheat | APOGEE_CUSTOM |
2366 | VAV with CO2 Monitoring - Parallel Fan Powered with Electric Reheat | APOGEE_CUSTOM |
2367 | VAV with CO2 Monitoring - Parallel Fan Powered with Hot Water Reheat | APOGEE_CUSTOM |
2368 | CV RPC with Hot Water Reheat, Relative Humidity and 3–position Switch | APOGEE_CUSTOM |
2369 | VAV with Revised Fan Operation | APOGEE_CUSTOM |
2370 | VAV with Expanded Room Temperature Range - Cooling Only | APOGEE_CUSTOM |
2371 | VAV with Expanded Room Temperature Range - Cooling and Heating | APOGEE_CUSTOM |
2372 | VAV with Expanded Room Temperature Range-Electric Heat or Baseboard Radiation | APOGEE_CUSTOM |
2373 | VAV with Expanded Room Temperature Range - Hot Water Reheat | APOGEE_CUSTOM |
2374 | VAV with Expanded Room Temperature Range - Fan Powered with Electric Reheat | APOGEE_CUSTOM |
2375 | VAV with Expanded Room Temperature Range - Fan Powered with Hot Water Reheat | APOGEE_CUSTOM |
2376 | VAV with Expanded Room Temperature Range - Parallel Fan Powered with Electric Reheat | APOGEE_CUSTOM |
2377 | VAV with Expanded Room Temperature Range - Parallel Fan Powered with Hot Water Reheat | APOGEE_CUSTOM |
2378 | Unit Condoner With Potentiometer Control of Damper | APOGEE_CUSTOM |
2380 | Slave Mode | APOGEE_P1 |
2381 | RPC Pneumatic with BTU Compensation - Slave Mode | APOGEE_LABS |
2382 | VAV with Dehumidification - Slave Mode | APOGEE_P1 |
2383 | LRC Pneumatic Application 2383 - Slave Mode | APOGEE_LABS |
2384 | UV 2–position Hot Water and Modulating Cold Water Valves - Slave Mode | APOGEE_P1 |
2385 | VAV with CO2 Monitoring - Slave Mode | APOGEE_P1 |
2387 | RPC Pneumatic with Humidity and 3–position Switch - Slave Mode | APOGEE_LABS |
2390 | Relative Humidity Controller - Slave Mode | APOGEE_P1 |
2391 | VAV with Hot Water Reheat and Humidity Control - Slave Mode | APOGEE_P1 |
2393 | Australian SPC - Slave Mode | APOGEE_P1 |
2394 | RPC Electronic with Humidity Control - Slave Mode | APOGEE_LABS |
2396 | Constant Volume with No Damper Cal - Slave Mode | APOGEE_P1 |
2397 | CAV Box Fan Coil Controller with optional VIV - Slave Mode | APOGEE_P1 |
2398 | Unit Vent with Humidity Control - Slave Mode | APOGEE_P1 |
2399 | Heat Pump 1 Cmpr and Dehumidification - Slave Mode | APOGEE_P1 |
2400 | Fan Coil with DI Pulse Accumulator | APOGEE_CUSTOM |
2401 | VAV Series Fan Powered Cooling Control | APOGEE_P1 |
2402 | LRC Electric with BTU Compensation | APOGEE_CUSTOM |
2403 | VAV with Revised Fan Logic | APOGEE_CUSTOM |
2404 | Fan Coil 2-pipe with 3–speed Fan | APOGEE_CUSTOM |
2406 | Unit Conditioner Cooling with Motion Sensor | APOGEE_CUSTOM |
2408 | Static Pressure Controller | APOGEE_CUSTOM |
2409 | Fan Coil with Fan Proof, Dis Temperature Alarm and Cond Alarm | APOGEE_CUSTOM |
2410 | Lab Room Controller for the Venturi Valve | APOGEE_LABS |
2411 | Asia Pacific 3–speed Fan Coil Controller | APOGEE_CUSTOM |
2412 | Unit Vent with Modulating Face and Bypass Control | APOGEE_CUSTOM |
2413 | Hines VAV with Variable Speed Series Fan, Electric Heat | APOGEE_CUSTOM |
2414 | VAV Parallel Fan Powered with Electric Reheat and Modified Damper Sequence | APOGEE_P1 |
2415 | VAV with Calibratable RTD | APOGEE_CUSTOM |
2416 | VAV Room Pressure Controller with Hot Water Reheat and 2" WC | APOGEE_CUSTOM |
2417 | CAV with Calibratable RTD | APOGEE_CUSTOM |
2418 | CV Room Pressure Controller with HW Reheat and 2" WC | APOGEE_LABS |
2419 | Fan Coil with Calibratable third–party RTD | APOGEE_CUSTOM |
2420 | VAV Cooling Only 2" WC | APOGEE_CUSTOM |
2421 | VAV Cooling or Heating 2" WC | APOGEE_CUSTOM |
2422 | VAV with Electric Reheat of Baseboard Radiation 2" WC | APOGEE_CUSTOM |
2423 | VAV with Hot Water Reheat 2" WC | APOGEE_CUSTOM |
2424 | VAV Series Fan Powered with Electric Reheat 2" WC | APOGEE_CUSTOM |
2425 | VAV Series Fan Powered with Hot Water Reheat 2" WC | APOGEE_CUSTOM |
2426 | VAV Parallel Fan Powered with Electric Reheat 2" WC | APOGEE_CUSTOM |
2427 | VAV Parallel Fan Powered with Hot Water Reheat 2" WC | APOGEE_CUSTOM |
2428 | Fan Coil with Calibratable RTD | APOGEE_CUSTOM |
2429 | Series Fan VAV – Option for 0-10V Fan Speed Control with Hot Water Reheat, Spare AIs and AOVs, Optional Night Damper, and 2 AVS | APOGEE_CUSTOM |
2430 | Constant Volume Cooling Only with 2" WC | APOGEE_CUSTOM |
2431 | Disch Temperature Control with Room-Load Heat/Cool Switchover | APOGEE_CUSTOM |
2432 | Constant Volume with Electric Reheat and 2" WC | APOGEE_CUSTOM |
2433 | Constant Volume with Hot Water Reheat and 2" WC | APOGEE_CUSTOM |
2434 | Fan Coil Unit with 3–stage Cooling and Hot Water Heat | APOGEE_CUSTOM |
2435 | Fan Coil Unit Cooling and Electric Heat with Pulse Counter | APOGEE_CUSTOM |
2436 | Pulse Counter | APOGEE_CUSTOM |
2437 | LRC with GDE 131 Actuation - Single Blade VAV | APOGEE_CUSTOM |
2438 | LRC with GDE 161 Actuation and Venturi Air Valve | APOGEE_CUSTOM |
2439 | LRC with GDE 161 Actuation - VFD Sup and Venturi Exhaust | APOGEE_LABS |
2448 | Unit Vent Heating/Cooling with Floating Outputs | APOGEE_CUSTOM |
2449 | LRC with Vortex Shedding and Analog Actuators | APOGEE_CUSTOM |
2450 | VAV Parallel Fan, Hot Water Reheat with AZM on DO5 | APOGEE_P1 |
2451 | LRC Slow Actuation with BTU Compensation | APOGEE_CUSTOM |
2452 | VAV Application 2026 with Modified Fan Operation | APOGEE_CUSTOM |
2453 | LRC Dual Duct VAV/CV with BTU Compensation | APOGEE_CUSTOM |
2455 | UV 2 position Hot Water and Modulating Cold Water Valves | APOGEE_CUSTOM |
2456 | LRC Venturi with BTU Compensation | APOGEE_CUSTOM |
2457 | VAV VSD Series Fan and 3–stage Electric Heat | APOGEE_CUSTOM |
2458 | LRC VAV GDE Actuation on OAVS | APOGEE_CUSTOM |
2459 | Slave Mode LRC, Slow Actuation | APOGEE_CUSTOM |
2460 | Water to Air Heat Pump with 1-stage Electric Heat, Multi-Speed Fan and Motion Sensor | APOGEE_CUSTOM |
2461 | Lighting Ctrl with Low Voltage Pulsed Relays | APOGEE_CUSTOM |
2462 | Lighting Ctrl with Low Voltage Maintained Relays | APOGEE_CUSTOM |
2463 | Pressurized Room Controller (PRC) | APOGEE_CUSTOM |
2464 | VAV - CO2 Alarming, HW Reheat and Radiation | APOGEE_CUSTOM |
2465 | Pressurized Room Controller (PRC) – Slave Mode | APOGEE_LABS |
2466 | Lighting Ctrl with Low Voltage Relays – Slave Mode | APOGEE_P1 |
2468 | LRC, Slow Actuation on OAVS Hot Water | APOGEE_LABS |
2469 | VAV VSD Series Fan - Slave Mode | APOGEE_P1 |
2470 | LRC Venturi with BTU Compensation - Slave Mode | APOGEE_LABS |
2472 | LRC Dual Duct VAV/CV with BTU Compensation - Slave Mode | APOGEE_LABS |
2473 | VAV Terminal Box Controller - Slave Mode | APOGEE_ATEC |
2474 | LRC Slow Actuation with BTU Compensation - Slave Mode | APOGEE_LABS |
2475 | LRC with Vortex Shedding and Analog Act - Slave Mode | APOGEE_LABS |
2476 | Unit Vent Heating/Cooling with Floating Outputs - Slave Mode | APOGEE_P1 |
2477 | LRC with GDE 131 Actuation - Slave Mode | APOGEE_LABS |
2478 | LRC with GDE 161 Actuation and Venturi - Slave Mode | APOGEE_LABS |
2479 | LRC with GDE 161 Actuation - VFD Sup - Slave Mode | APOGEE_LABS |
2481 | VAV with Calibratable RTD - Slave Mode | APOGEE_P1 |
2482 | CAV with Calibratable RTD - Slave Mode | APOGEE_P1 |
2483 | Fan Coil with Calibratable RTD - Slave Mode | APOGEE_P1 |
2484 | Hines VAV with Variable Speed Ser Fan, Electric Heat - Slave Mode | APOGEE_P1 |
2485 | FCU with 3–stage Cooling and Hot Water Heat - Slave Mode | APOGEE_P1 |
2486 | COVAV Demo Application 2486 | APOGEE_ATEC |
2488 | VAV with 0-10V Series-Fan Speed and Hot Water Reheat - Slave Mode | APOGEE_P1 |
2490 | Fan Coil with DI Pulse Accumulator - Slave Mode | APOGEE_P1 |
2491 | Static Pressure Controller - Slave Mode | APOGEE_P1 |
2492 | FC with Fan Proof, Dis Temperature Alarm, Cond Alarm - Slave Mode | APOGEE_P1 |
2495 | Asia Pacific 3–speed Fan Coil Controller - Slave Mode | APOGEE_P1 |
2497 | TEC with Expanded Point I/O | APOGEE_CUSTOM |
2499 | VAV - CO2 Alarming, Hot Water Reheat and Radiation – Slave Mode | APOGEE_P1 |
2500 | VAV Cooling Only | APOGEE_ATEC |
2501 | VAV Cooling or Heating | APOGEE_ATEC |
2502 | CV AHU with 2–position 100% OA Damper, SA temperature, Cold Water Cooling/Hot Water Heating | APOGEE_CUSTOM |
2503 | CV AHU with 2–position 100% OA Damper, Cold Water Cooling/Hot Water Heating | APOGEE_CUSTOM |
2510 | VAV Cooling Only | APOGEE_BTEC |
2511 | VAV Cooling and Heating | APOGEE_BTEC |
2512 | VAV with Electric Heat or Baseboard Radiation | APOGEE_BTEC |
2513 | VAV with Hot Water Heat | APOGEE_BTEC |
2514 | VAV Series Fan and Electric Heat | APOGEE_BTEC |
2515 | VAV Series or Parallel Fan and Hot Water Reheat | APOGEE_BTEC |
2516 | VAV Parallel Fan and Electric Heat | APOGEE_BTEC |
2517 | VAV with Hot Water Heat and Parallel Fan | APOGEE_BTEC |
2520 | COVAV Demo Application 2520 | APOGEE_ATEC |
2521 | COVAV Demo Application 2521 | APOGEE_ATEC |
2522 | VAV with Electric Reheat | APOGEE_ATEC |
2523 | VAV with Hot Water Reheat | APOGEE_ATEC |
2524 | VAV Series Fan Powered with Electric Reheat | APOGEE_ATEC |
2526 | VAV Parallel Fan Powered with Electric Reheat | APOGEE_ATEC |
2528 | VAV Pressure Dependent Cooling or Heating | APOGEE_BTEC |
2529 | VAV Pressure Dependent with 1 or 2 Valve Hot Water Reheat | APOGEE_BTEC |
2530 | VAV Cooling Only | APOGEE_BTEC |
2531 | VAV Cooling or Heating | APOGEE_BTEC |
2532 | VAV with Electric Reheat | APOGEE_BTEC |
2533 | VAV with Hot Water Reheat | APOGEE_BTEC |
2534 | VAV Series Fan Powered with Electric Reheat | APOGEE_BTEC |
2535 | VAV Series Fan Powered with Hot Water Reheat | APOGEE_BTEC |
2536 | VAV Parallel Fan Powered with Electric Reheat | APOGEE_BTEC |
2537 | VAV Parallel Fan Powered with Hot Water Reheat | APOGEE_BTEC |
2540 | Unit Cond VAV Pressure Dependent Cooling or Heating | APOGEE_BTEC |
2541 | Unit Cond VAV Pressure Dependent Hot Water Reheat | APOGEE_BTEC |
2542 | Fan Coil Unit 2-pipe Cool/Heat with Optional Heating Valve | APOGEE_BTEC |
2543 | Fan Coil Unit Cooling and Heating | APOGEE_BTEC |
2544 | Fan Coil Unit 2-stage Cooling and Electric Reheat | APOGEE_BTEC |
2545 | Fan Coil Unit 2-stage Cooling and Hot Water Reheat | APOGEE_BTEC |
2546 | Fan Coil Unit Cooling and Electric Heat | APOGEE_BTEC |
2549 | BACnet Heat Pump – Slave Mode | APOGEE_BTEC |
2550 | Fan Coil Cooling and Heating | APOGEE_BTEC |
2551 | Fan Coil Cooling and Heating | APOGEE_BTEC |
2552 | Fan Coil Cooling and Electric Heat | APOGEE_BTEC |
2553 | Fan Coil 2–stage Cooling and Hot Water Reheat | APOGEE_BTEC |
2554 | Fan Coil Cooling and Electric Heat | APOGEE_BTEC |
2557 | VAV VSD Series Fan and 3–stage Electric Heat | APOGEE_CUSTOM |
2558 | BCNT VAV DCV (CO2) and Chilled Beam | APOGEE_CUSTOM |
2560 | VAV Cooling Only | APOGEE_ATEC |
2561 | VAV Cooling or Heating | APOGEE_ATEC |
2562 | VAV with Electric Reheat | APOGEE_ATEC |
2563 | VAV with Hot Water Reheat | APOGEE_ATEC |
2564 | VAV Series Fan Powered with Electric Reheat | APOGEE_ATEC |
2565 | VAV Series Fan Powered with Hot Water Reheat | APOGEE_ATEC |
2566 | VAV Parallel Fan Powered with Electric Reheat | APOGEE_ATEC |
2567 | VAV Parallel Fan Powered with Hot Water Reheat | APOGEE_ATEC |
2573 | Heat Pump Multi-Stage with Reversing Valve Control | APOGEE_BTEC |
2574 | Heat Pump Multi-Stage without Reversing Valve Control | APOGEE_BTEC |
2575 | BCNT UV Heating Cold Water Cooling ASHRAE Cycle I, II | APOGEE_BTEC |
2576 | BCNT UV Heating Cold Water Cooling ASHRAE Cycle III | APOGEE_BTEC |
2577 | BCNT UV Heating DX Cooling ASHRAE Cycle I and II | APOGEE_BTEC |
2578 | BCNT UV Heating DX Cooling ASHRAE Cycle III | APOGEE_BTEC |
2579 | BCNT UV Heating Cooling NESBITT Cycle W | APOGEE_BTEC |
2580 | VAV CO2 with AOV or Floating Heat | APOGEE_CUSTOM |
2581 | VAV Series Fan with CO2, AOV or Floating Heat | APOGEE_CUSTOM |
2582 | VAV Parallel Fan with CO2, AOV or Floating Heat | APOGEE_CUSTOM |
2583 | BCNT HP MultiCompr Mixed Air Reverse Valve Control | APOGEE_CUSTOM |
2584 | BCNT HP HtgClg with Mixed Air and Internal Reverse Valve | APOGEE_CUSTOM |
2585 | Fan Coil Unit Conditioner - Slave Mode | APOGEE_BTEC |
2586 | VAV Terminal Box Controller - Slave Mode | APOGEE_BTEC |
2587 | TEC - Slave mode Electronic Output with Secure Mode | APOGEE_BTEC |
2588 | CV AHU with 2 Position 100% OA Damper - Slave Mode | APOGEE_BTEC |
2590 | Heat Pump Multi-Stage - Slave Mode | APOGEE_BTEC |
2591 | Unit Conditioner - Slave Mode | APOGEE_BTEC |
2592 | Slave Mode BCNT VAV DCV (CO2) Chill Beam | APOGEE_LABS |
2593 | BCNT HP MultiCompr Mixed Air Reverse Valve Control | APOGEE_BTEC |
2594 | BCNT HP HtgClg with Mixed Air and Internal Reverse Valve | APOGEE_BTEC |
2595 | BACnet Unit Vent - Slave Mode | APOGEE_BTEC |
2596 | TEC with Expanded Point I/O | APOGEE_BTEC |
2597 | VAV Terminal Box Controller - Slave Mode | APOGEE_ATEC |
2598 | BACnet VAV with CO2 Monitoring | APOGEE_BTEC |
2599 | VAV VSD Series Fan - Slave Mode | APOGEE_BTEC |
2600 | Slave Mode | APOGEE_LABS |
2601 | VAV with Reheat - One Exhaust, One Supply | APOGEE_LABS |
2602 | VAV with Reheat - No Exhaust, One or Two Supplies | APOGEE_LABS |
2603 | VAV Dual-Duct - One Exhaust, One Supply | APOGEE_LABS |
2611 | VAV with Reheat - One Exhaust, One Supply | APOGEE_LABS |
2612 | VAV with Reheat - No Exhaust, One or Two Supplies | APOGEE_LABS |
2613 | VAV Dual-Duct - One Exhaust, One Supply | APOGEE_LABS |
2620 | LRC VAV Room Pressurization with Hot Water Reheat and Two Venturi Valves | APOGEE_LABS |
2621 | VAV Room Pressurization with Hot Water Reheat - One Exhaust, One Supply | APOGEE_LABS |
2622 | VAV Room Pressurization with Hot Water Reheat and Slow Venturi Air Valves, One Exhaust, One Supply | APOGEE_LABS |
2623 | LCM-OAVS Damper Slow RTS | APOGEE_LABS |
2624 | LCM-OAVS with Slow Supply Damper Actuation and Slow Exhaust Venturi Air Valve | APOGEE_LABS |
2626 | LRC VAV with Hot Water Reheat, BTU Compensation and Two Venturi Valves | APOGEE_LABS |
2627 | VAV Room Press with BTU Compensation, Hot Water Reheat and Fast Actuation | APOGEE_LABS |
2628 | VAV Room Pressurization with Hot Water Reheat and Slow Venturi Air Valves, One Exhaust, One Supply - includes BTU Compensation | APOGEE_LABS |
2629 | LCM-OAVS Damper Slow BTU | APOGEE_LABS |
2630 | LCM-OAVS with Slow Supply Damper Actuation and Slow Exhaust Venturi Air Valve - includes BTU Compensation | APOGEE_LABS |
2631 | PRC-OAVS with Pressurization Control by Differential Flow Reset, with Heating by BTU Compensation - Slow Actuation, Floating or Analog Output | APOGEE_LABS |
2697 | LCM-OAVS Damper Slow RTS/BTU - Slave Mode | APOGEE_LABS |
2698 | VAV Room Press with Hot Water Reheat - Slave Mode | APOGEE_LABS |
2699 | LRC VAV Room Press for Venturi Valves - Slave Mode | APOGEE_LABS |
2700 | ABB ACH 500 Adjustable Frequency AC Drive | APOGEE_INT |
2701 | MagneTek GPD 505 Adjustable Frequency AC Drive | APOGEE_INT |
2703 | Graham VLT 3500 Adjustable Frequency AC Drive | APOGEE_INT |
2705 | Square D ALTIVAR 66 Adjustable Frequency AC Drive | APOGEE_INT |
2706 | Saftronics FP5 Adjustable Frequency AC Drive | APOGEE_INT |
2707 | ABB ACS 600 Adjustable Frequency AC Drive | APOGEE_INT |
2708 | ABB ACH 400 Adjustable Frequency AC Drive | APOGEE_INT |
2709 | VLT6000 HVAC | APOGEE_INT |
2710 | Reliance VTAC 7 Adjustable Frequency AC Drive | APOGEE_INT |
2711 | GE/Fuji AF$300 Adjustable Frequency AC Drive | APOGEE_INT |
2712 | Magnetek GPD 506 VFD | APOGEE_INT |
2713 | HV9000 VFD | APOGEE_INT |
2714 | Toshiba E3 Adjustable Frequency AC Drive | APOGEE_INT |
2715 | SquareD Altivar 58 | APOGEE_INT |
2717 | SIEMENS ECO VSD | APOGEE_INT |
2718 | Rockwell/Reliance VTAC9 VFD | APOGEE_INT |
2719 | ABB ACH400 VSD Direct Connect | APOGEE_INT |
2720 | GE Fuji AF-300 G11/P11 Adjustable AC Drive | APOGEE_INT |
2721 | Yaskawa Electric America E7 | APOGEE_INT |
2722 | SIEMENS SED2 | APOGEE_INT |
2723 | ABB ACS 600 VSD | APOGEE_INT |
2724 | ABB ACH 400 VSD | APOGEE_INT |
2726 | AC Tech MCH Variable Speed AC Drive | APOGEE_INT |
2728 | Hitachi L300P Series Inverter | APOGEE_INT |
2729 | Hitachi L100 Series Inverter Drive | APOGEE_INT |
2730 | Hitachi J300 Series Inverter Drive | APOGEE_INT |
2731 | Eurotherm HVAC10 AC Drive/690+ Series | APOGEE_INT |
2732 | TB Wood WF2 Sensorless Vector Drive | APOGEE_INT |
2733 | GE Fuji AF-300 F11 Adjustable AC Drive | APOGEE_INT |
2734 | ABB ACH550 Frequency Drive | APOGEE_INT |
2735 | Allen Bradley | APOGEE_INT |
2736 | Toshiba Q7 2736 | APOGEE_INT |
2737 | E-Clipse Bypass Adjustable Frequency AC Drive Bypass Option | APOGEE_INT |
2738 | Toshiba VF-FS1 | APOGEE_INT |
2741 | Mitsubishi F700 | APOGEE_INT |
2742 | SIEMENS SED2 | APOGEE_INT |
2743 | Cutler-Hammer SVX9000 | APOGEE_INT |
2744 | ABB_ACS800 | APOGEE_INT |
2747 | Lumisys Lighting | APOGEE_INT |
2750 | Mitsubishi XLTR200 | APOGEE_INT |
2759 | DanFoss VLT F100 | APOGEE_INT |
2770 | SI BT300 Frequency Drive | APOGEE_INT |
2771 | PM50A | APOGEE_INT |
2772 | PM1000A | APOGEE_INT |
2773 | PM100A | APOGEE_INT |
2774 | PM200A | APOGEE_INT |
2775 | PM400A | APOGEE_INT |
2776 | VULCAIN VA901TCO 2776 | APOGEE_INT |
2777 | VALCAIN VA901TCO 2777 | APOGEE_INT |
2778 | VALCAIN VA901TCO 2778 | APOGEE_INT |
2779 | VULCAIN VA901TCO 2779 | APOGEE_INT |
2780 | Litrol Lighting Control MLC48R38G | APOGEE_INT |
2781 | Litrol Lighting Control MLC46R24G24I | APOGEE_INT |
2782 | Litrol Lighting Control MLC46R48I | APOGEE_INT |
2783 | Litrol Lighting Control MLC48R40I | APOGEE_INT |
2784 | Litrol Lighting Control MLC46G48I | APOGEE_INT |
2785 | Litrol Lighting Control MLC48G40I | APOGEE_INT |
2786 | Litrol Lighting Control MLC46P48I | APOGEE_INT |
2787 | Litrol Lighting Control MLC48P40I | APOGEE_INT |
2788 | Litrol Lighting Control MLC48R24G12P | APOGEE_INT |
2793 | MSA ZGARD Sensor | APOGEE_INT |
2794 | VULCAIN VA901TCO 2794 | APOGEE_INT |
2803 | UAP Paris Special, Single Duct | APOGEE_INT |
2804 | UAP Paris Special, Dual Duct | APOGEE_INT |
2812 | UAP Paris Special - Slave Mode | APOGEE_INT |
2817 | Lab Press Controller with Hot Water Reheat | APOGEE_LABS |
2822 | Lighting Control 2 Circuits with Electric Reheat | APOGEE_INT |
2830 | Lighting Control 3 Circuits with VAV | APOGEE_INT |
2833 | Lighting Control 3 Circuits with VAV and Hot Water Reheat | APOGEE_INT |
2843 | VAV 0-10 Heat and CO2 Monitor | APOGEE_CUSTOM |
2845 | VAV Series Fan AO Heat CO2 | APOGEE_CUSTOM |
2847 | VAV Parallel Fan AO Heat CO2 | APOGEE_CUSTOM |
2849 | BACnet Heat Pump Slave Mode | APOGEE_ATEC |
2855 | Fan Coil 2-pipe Htg/Clg with Optional Cooling Valve and Electric Heating | APOGEE_P1 |
2860 | VAV Cooling Only | APOGEE_ATEC |
2861 | VAV Cooling or Heating | APOGEE_ATEC |
2862 | VAV with Electric Reheat | APOGEE_ATEC |
2863 | VAV with Hot Water Reheat | APOGEE_ATEC |
2864 | VAV Series Fan Powered with Electric Reheat | APOGEE_ATEC |
2865 | VAV Series Fan Powered with Hot Water Reheat | APOGEE_ATEC |
2866 | VAV Parallel Fan Powered with Hot Water Reheat | APOGEE_ATEC |
2867 | VAV Parallel Fan Powered with Hot Water Reheat | APOGEE_ATEC |
2891 | Lighting Controller - Slave Mode | APOGEE_P1 |
2893 | BCNT HP MultiCompr Mixed Air Reverse Valve Control | APOGEE_ATEC |
2894 | BCNT HP HtgClg with Mixed Air and Internal Reverse Valve | APOGEE_ATEC |
2897 | VAV Terminal Box Controller - Slave Mode | APOGEE_ATEC |
2899 | VAV AO Heat and CO2 Monitor – Slave Mode | APOGEE_P1 |
2917 | Lab Press Controller with Hot Water Reheat and Dew Point Sensor | APOGEE_LABS |
4000 | RTU General | APOGEE_INT |
4001 | RTU_DAC | APOGEE_INT |
4002 | RTU_SCC | APOGEE_INT |
4003 | SCUC | APOGEE_INT |
4010 | UV General ver 1 | APOGEE_INT |
4011 | UV Model 0 ver 1 | APOGEE_INT |
4012 | UV Model 2 ver 1 | APOGEE_INT |
4013 | UV Model 3 ver 1 | APOGEE_INT |
4014 | UV Model 4 ver 1 | APOGEE_INT |
4015 | UV Model 5 ver 1 | APOGEE_INT |
4016 | UV Model 6 ver 1 | APOGEE_INT |
4017 | UV Model 7 ver 1 | APOGEE_INT |
4018 | UV Model 8 ver 1 | APOGEE_INT |
4019 | UV Model 9 ver 1 | APOGEE_INT |
4020 | UV Model 10 ver1 | APOGEE_INT |
4021 | UV Model 11 ver1 | APOGEE_INT |
4022 | UV Model 12 ver1 | APOGEE_INT |
4023 | UV Model 13 ver1 | APOGEE_INT |
4024 | UV Model 14 ver1 | APOGEE_INT |
4025 | UV Model 15 ver1 | APOGEE_INT |
4026 | UV Model 16 ver1 | APOGEE_INT |
4027 | UV Model 17 ver1 | APOGEE_INT |
4028 | UV Model 18 ver1 | APOGEE_INT |
4029 | Centrifugal | APOGEE_INT |
4030 | AC Global Scroll | APOGEE_INT |
4031 | AC Scroll | APOGEE_INT |
4032 | AC Global Screw | APOGEE_INT |
4033 | WC Global Scroll | APOGEE_INT |
4034 | Chiller General | APOGEE_INT |
4050 | ECO2 | APOGEE_INT |
4053 | YT STD V2 | APOGEE_INT |
4054 | YT SSS V2 | APOGEE_INT |
4055 | YT VSD V2 | APOGEE_INT |
4056 | YK STD V2 | APOGEE_INT |
4057 | YK SSS V2 | APOGEE_INT |
4058 | YK VSD V2 | APOGEE_INT |
4059 | YCAS MSTR V2 | APOGEE_INT |
4060 | YCAS SLV V2 | APOGEE_INT |
4061 | YCWS V2 | APOGEE_INT |
4062 | YCAL 2050 | APOGEE_INT |
4063 | YCAL TEMP | APOGEE_INT |
4064 | YCAL SUCT | APOGEE_INT |
4065 | YR STD | APOGEE_INT |
4066 | YR SSS | APOGEE_INT |
4067 | YS STD | APOGEE_INT |
4068 | YS SSS | APOGEE_INT |
4098 | Comm Fail | APOGEE_INT |
4099 | Diagnostic | APOGEE_INT |
4100 | UV General ver 2 | APOGEE_INT |
4101 | UV Model 0 ver 2 | APOGEE_INT |
4102 | UV Model 2 ver 2 | APOGEE_INT |
4103 | UV Model 3 ver 2 | APOGEE_INT |
4104 | UV Model 4 ver 2 | APOGEE_INT |
4105 | UV Model 5 ver 2 | APOGEE_INT |
4106 | UV Model 6 ver 2 | APOGEE_INT |
4107 | UV Model 7 ver 2 | APOGEE_INT |
4108 | UV Model 8 ver 2 | APOGEE_INT |
4109 | UV Model 9 ver 2 | APOGEE_INT |
4110 | UV Model 10 ver2 | APOGEE_INT |
4111 | UV Model 11 ver2 | APOGEE_INT |
4112 | UV Model 12 ver2 | APOGEE_INT |
4113 | UV Model 13 ver2 | APOGEE_INT |
4114 | UV Model 14 ver2 | APOGEE_INT |
4115 | UV Model 15 ver2 | APOGEE_INT |
4116 | UV Model 16 ver2 | APOGEE_INT |
4117 | UV Model 17 ver2 | APOGEE_INT |
4118 | UV Model 18 ver2 | APOGEE_INT |
4120 | RTU2 General | APOGEE_INT |
4121 | RTU2_DAC | APOGEE_INT |
4122 | RTU2_SCC | APOGEE_INT |
4123 | SCUC2 | APOGEE_INT |
4125 | RTU V3 DAC | APOGEE_INT |
4126 | RTU V3 SCC | APOGEE_INT |
4127 | SCUC V3 DAC | APOGEE_INT |
4128 | SCUC V3 SCC | APOGEE_INT |
4130 | UV GEN V3 ENG | APOGEE_INT |
4131 | UV MOD 0 V3 ENG | APOGEE_INT |
4132 | UV MOD 2 V3 ENG | APOGEE_INT |
4133 | UV MOD 3 V3 ENG | APOGEE_INT |
4134 | UV MOD 4 V3 ENG | APOGEE_INT |
4135 | UV MOD 5 V3 ENG | APOGEE_INT |
4136 | UV MOD 6 V3 ENG | APOGEE_INT |
4137 | UV MOD 7 V3 ENG | APOGEE_INT |
4138 | UV MOD 8 V3 ENG | APOGEE_INT |
4139 | UV MOD 9 V3 ENG | APOGEE_INT |
4140 | UV MOD10 V3 ENG | APOGEE_INT |
4141 | UV MOD11 V3 ENG | APOGEE_INT |
4142 | UV MOD12 V3 ENG | APOGEE_INT |
4143 | UV MOD13 V3 ENG | APOGEE_INT |
4144 | UV MOD14 V3 ENG | APOGEE_INT |
4145 | UV MOD15 V3 ENG | APOGEE_INT |
4146 | UV MOD16 V3 ENG | APOGEE_INT |
4147 | UV MOD17 V3 ENG | APOGEE_INT |
4148 | UV MOD18 V3 ENG | APOGEE_INT |
4150 | MS 20,30,50 STD | APOGEE_INT |
4151 | MS 20,30,50 HR | APOGEE_INT |
4152 | MS 20,30,50 HP | APOGEE_INT |
4153 | MS 70,90 STD | APOGEE_INT |
4160 | RTU S100 V4 DAC | APOGEE_INT |
4161 | RTU S100 V4 SCC | APOGEE_INT |
4162 | RTU S200 V4 DAC | APOGEE_INT |
4163 | RTU S200 V4 SCC | APOGEE_INT |
4180 | DAC | APOGEE_INT |
4181 | SCC | APOGEE_INT |
4300 | BTEC 2510 | APOGEE_INT |
4301 | BTEC 2511 | APOGEE_INT |
4302 | BTEC 2512 | APOGEE_INT |
4303 | BTEC 2513 | APOGEE_INT |
4304 | BTEC 2514 | APOGEE_INT |
4305 | BTEC 2515 | APOGEE_INT |
4306 | BTEC 2516 | APOGEE_INT |
4307 | BTEC 2517 | APOGEE_INT |
4308 | BTEC 2587 | APOGEE_INT |
4310 | BTEC 2573 | APOGEE_INT |
4311 | BTEC 2574 | APOGEE_INT |
4312 | BTEC 2590 | APOGEE_INT |
4313 | BUV 2575 | APOGEE_INT |
4314 | BUV 2576 | APOGEE_INT |
4315 | BUV 2577 | APOGEE_INT |
4316 | BUV 2578 | APOGEE_INT |
4317 | BUV 2579 | APOGEE_INT |
4318 | BUV 2595 | APOGEE_INT |
4320 | BTEC 2540 | APOGEE_INT |
4321 | BTEC 2541 | APOGEE_INT |
4322 | BTEC 2550 | APOGEE_INT |
4323 | BTEC 2551 | APOGEE_INT |
4324 | BTEC 2552 | APOGEE_INT |
4325 | BTEC 2553 | APOGEE_INT |
4326 | BTEC 2554 | APOGEE_INT |
4327 | BTEC 2591 | APOGEE_INT |
4340 | BTEC 2510 | APOGEE_INT |
4341 | BTEC 2511 | APOGEE_INT |
4342 | BTEC 2512 | APOGEE_INT |
4343 | BTEC 2513 | APOGEE_INT |
4344 | BTEC 2514 | APOGEE_INT |
4345 | BTEC 2515 | APOGEE_INT |
4346 | BTEC 2516 | APOGEE_INT |
4347 | BTEC 2517 | APOGEE_INT |
4348 | BTEC 2587 | APOGEE_INT |
4349 | BTEC 2540 | APOGEE_INT |
4350 | BTEC 2541 | APOGEE_INT |
4351 | BTEC 2550 | APOGEE_INT |
4352 | BTEC 2551 | APOGEE_INT |
4353 | BTEC 2552 | APOGEE_INT |
4354 | BTEC 2553 | APOGEE_INT |
4355 | BTEC 2554 | APOGEE_INT |
4356 | BTEC 2591 | APOGEE_INT |
4357 | BTEC 2573 | APOGEE_INT |
4358 | BTEC 2574 | APOGEE_INT |
4359 | BTEC 2590 | APOGEE_INT |
4500 | MB DIAG | APOGEE_INT |
4501 | SQD PM600 | APOGEE_INT |
4502 | SQD BCM42 | APOGEE_INT |
4503 | SQD CM3000 | APOGEE_INT |
4504 | SQD G3 2BUS | APOGEE_INT |
4505 | SQD G3 4BUS | APOGEE_INT |
4506 | SQD G3 6BUS | APOGEE_INT |
4507 | SQD G3 8BUS | APOGEE_INT |
4508 | SQD MCM8364 | APOGEE_INT |
4509 | SQD ALTIVAR58 | APOGEE_INT |
4510 | SQDL PM600BASIC | APOGEE_INT |
4511 | SQDL PM600MIN | APOGEE_INT |
4512 | SQDL PM600MAX | APOGEE_INT |
4513 | SQDL PM600ENGY | APOGEE_INT |
4514 | SQDL BCM42BASIC | APOGEE_INT |
4515 | SQDL BCM42BRKSZ | APOGEE_INT |
4516 | SQDL BCM42THRSH | APOGEE_INT |
4517 | SQDL BCM42TMDLY | APOGEE_INT |
4518 | SQDL CM3000RT1 | APOGEE_INT |
4519 | SQDL CM3000RT2 | APOGEE_INT |
4520 | SQDL CM3000PWRQ | APOGEE_INT |
4521 | SQDL CM3000MIN | APOGEE_INT |
4522 | SQDL CM3000MAX | APOGEE_INT |
4523 | SQDL CM3000ENGY | APOGEE_INT |
4524 | SQDL G3GRPIP1 | APOGEE_INT |
4525 | SQDL G3GRPIP2 | APOGEE_INT |
4526 | SQDL G3BRKCTR | APOGEE_INT |
4529 | PM800 | APOGEE_INT |
4540 | SEA PM93XX | APOGEE_INT |
4541 | SEA PM9700 | APOGEE_INT |
4542 | SEA PM9500 | APOGEE_INT |
4543 | SEA PM9200 | APOGEE_INT |
4544 | SEA PM4700 | APOGEE_INT |
4545 | SEA PM4720 | APOGEE_INT |
4546 | SEA PM4300 | APOGEE_INT |
4547 | SEA STATIC TRIP | APOGEE_INT |
4548 | SEA SAMMS | APOGEE_INT |
4549 | SEA SB TRIP | APOGEE_INT |
4550 | SEA LCP Panel | APOGEE_INT |
4551 | SEA LCP Global | APOGEE_INT |
4553 | SEA WL Breaker | APOGEE_INT |
4559 | SEA DTU Command | APOGEE_INT |
4591 | VACON VFD | APOGEE_INT |
4592 | HUNTAIR Standard | APOGEE_INT |
4621 | YT STD V2 | APOGEE_INT |
4622 | YT SSS V2 | APOGEE_INT |
4623 | YT VSD V2 | APOGEE_INT |
4624 | YK STD V2 | APOGEE_INT |
4625 | YK SSS V2 | APOGEE_INT |
4626 | YK VSD V2 | APOGEE_INT |
4627 | YCAS MSTR V2 | APOGEE_INT |
4629 | YCWS V2 | APOGEE_INT |
4630 | YCAL 2050 | APOGEE_INT |
4631 | YCAL TEMP | APOGEE_INT |
4632 | YCAL SUCT | APOGEE_INT |
4633 | YR STD | APOGEE_INT |
4634 | YR SSS | APOGEE_INT |
4635 | YS STD | APOGEE_INT |
4636 | YS SSS | APOGEE_INT |
4640 | AZL52 Hot Water | APOGEE_INT |
4641 | AZL52 Steam | APOGEE_INT |
4642 | AZL51 Hot Water | APOGEE_INT |
4643 | AZL51 Steam | APOGEE_INT |
4644 | RWF40 | APOGEE_INT |
4650 | CLIMATIC 50 | APOGEE_INT |
4990 | Modbus Slave | APOGEE_INT |
5120 | 19XL Chiller Controller | APOGEE_INT |
5121 | 19EX Chiller Controller | APOGEE_INT |
5122 | 19XR Chiller Controller | APOGEE_INT |
5123 | 23XL Chiller Controller | APOGEE_INT |
5124 | 3200MP Single Chiller Controller | APOGEE_INT |
5125 | 3200MP Dual Chiller Controller | APOGEE_INT |
5126 | 19XR-2 Chiller Controller, Part 1 | APOGEE_INT |
5127 | 19XR-2 Chiller Controller, Part 2 | APOGEE_INT |
5128 | CHILLERVISOR System Manager II (CSM II) | APOGEE_INT |
5129 | CHILLERVISOR System Manager III (CSM III) | APOGEE_INT |
5130 | 30GT Chiller Controller | APOGEE_INT |
5131 | 30GN Chiller Controller | APOGEE_INT |
5132 | 30GN Maintenance | APOGEE_INT |
5133 | 30GX/HX Chiller Controller, Part 1 | APOGEE_INT |
5134 | 30GX/HX Chiller Controller, Part 2 | APOGEE_INT |
5135 | RTU 48/50 - EK, EJ, EW, EY | APOGEE_INT |
5136 | RTU 48/50 - NB, NP, Part 1 | APOGEE_INT |
5137 | RTU 48/50 - NB, NP, Part 2 | APOGEE_INT |
5138 | 16JT Absorption Chiller Controller | APOGEE_INT |
5139 | 17EX Centrifugal Chiller Controller | APOGEE_INT |
5320 | VVT - Monitor Thermostat (TM01) | APOGEE_INT |
5321 | VVT - Monitor Controller (VM32) | APOGEE_INT |
5322 | VVT - Zone Controller - Pressure Dependent (ZC01) | APOGEE_INT |
5323 | VVT - Zone Controller - Pressure Independent (ZCPI) | APOGEE_INT |
5324 | VVT - Bypass Controller (BC00) | APOGEE_INT |
5336 | 48/50 EJ/EK/EW/EY Rooftop Unit | APOGEE_INT |
5337 | Premier Link Controller | APOGEE_INT |
5338 | 48/50A Rooftop Unit 1 | APOGEE_INT |
5339 | 48/50A Rooftop Unit 2 | APOGEE_INT |
5470 | Diagnostic | APOGEE_INT |
5471 | DEVICESONLY | APOGEE_INT |
5472 | DEV Components | APOGEE_INT |
5473 | SUBMOD Devices | APOGEE_INT |
5474 | PSEUDOPOINTS | APOGEE_INT |
5475 | XLS SUB 1 50 | APOGEE_INT |
5476 | XLSSUB 51 99 | APOGEE_INT |
5600 | N2 Diagnostics | APOGEE_INT |
5601 | VAV Controller Test Application | APOGEE_INT |
5602 | UNT Controller Test Application | APOGEE_INT |
5603 | AHU Controller Test Application | APOGEE_INT |
5604 | DX9100 Controller Test Application | APOGEE_INT |
5607 | BIG MOMMA Application | APOGEE_INT |
5641 | Generic Input/Output (Point Multiplexer) | APOGEE_INT |
5642 | Generic Input/Output (Point Multiplexer) | APOGEE_INT |
5650 | JCI UNT GEN RTU | APOGEE_INT |
5700 | Diagnostic Application | APOGEE_INT |
5701 | AHU 100% OA Single Path (Constant DA Temperature) | APOGEE_INT |
5702 | AHU MA Single Path (Room Control) | APOGEE_INT |
5703 | AHU MA Single Path (Constant DA Temperature) | APOGEE_INT |
5704 | JCI AHU Controller Application | APOGEE_INT |
5705 | JCI AHU Controller Application | APOGEE_INT |
5706 | JCI AHU Controller Application | APOGEE_INT |
5707 | JCI AHU Controller Application | APOGEE_INT |
5708 | JCI AHU Controller Application | APOGEE_INT |
5709 | JCI AHU Controller Application | APOGEE_INT |
5710 | JCI AHU Controller Application | APOGEE_INT |
5712 | Diagnostics | APOGEE_INT |
5713 | FLO2 BLOCK | APOGEE_INT |
5714 | PEM1 BLOCK | APOGEE_INT |
5715 | MNFLO BLOCK | APOGEE_INT |
5716 | MN HP BLOCK | APOGEE_INT |
5717 | ZONE2 BLOCK | APOGEE_INT |
5718 | SGCM BLOCK | APOGEE_INT |
5719 | RLCM BLOCK | APOGEE_INT |
5751 | DX9100 Controller Application | APOGEE_INT |
5752 | DX9100 Controller Application | APOGEE_INT |
5753 | DX9100 Controller Application | APOGEE_INT |
5754 | DX9100 Controller Application | APOGEE_INT |
5800 | Data Air DAPII | APOGEE_INT |
5801 | Bell & Gossett Technologic 500 Speed Drive | APOGEE_INT |
5802 | B & G Slave Controller for Technologic 500 | APOGEE_INT |
5810 | Square D Series 600 Power meter - Basic | APOGEE_INT |
5811 | Square D Series 600 Power meter - Minimum Values | APOGEE_INT |
5812 | Square D Series 600 Power meter - Maximum Values | APOGEE_INT |
5813 | Square D Series 600 Power meter - Energy and Demand Values | APOGEE_INT |
5814 | Square D BCM42 Branch Current Monitor - Basic | APOGEE_INT |
5815 | Square D BCM42 Branch Current Monitor - Breaker Size Configuration | APOGEE_INT |
5816 | Square D BCM42 Branch Current Monitor - Threshold Configuration | APOGEE_INT |
5817 | Square D BCM42 Branch Current Monitor - Time Delay Configuration | APOGEE_INT |
5818 | Square D Circuit Monitor CM3000 and CM4000 - 100ms Real Time | APOGEE_INT |
5819 | Square D Circuit Monitor CM3000 and CM4000 - 1s Real Time | APOGEE_INT |
5820 | Square D Circuit Monitor CM3000 and CM4000 - Power Quality | APOGEE_INT |
5821 | Square D Circuit Monitor CM3000 and CM4000 - Minimum Metered Values | APOGEE_INT |
5822 | Square D Circuit Monitor CM3000 and CM4000 - Maximum Metered Values | APOGEE_INT |
5823 | Square D Circuit Monitor CM3000 and CM4000 - Energy | APOGEE_INT |
5824 | Square D G3 Lighting Control Panel - Group Input Control 1 | APOGEE_INT |
5825 | Square D G3 Lighting Control Panel - Group Input Control 2 | APOGEE_INT |
5826 | Square D G3 Lighting Control Panel - Breaker Control and Monitoring | APOGEE_INT |
5840 | Diagnostic | APOGEE_INT |
5841 | Steam Heating | APOGEE_INT |
5842 | Hot Water Heating | APOGEE_INT |
5843 | Hot Water Heating Rst | APOGEE_INT |
5850 | YEP Diagnostic | APOGEE_INT |
5851 | A1 MASTER | APOGEE_INT |
5852 | A3 SLAVE | APOGEE_INT |
5853 | C1 MASTER | APOGEE_INT |
5854 | C3 SLAVE | APOGEE_INT |
5855 | LS | APOGEE_INT |
5856 | RT | APOGEE_INT |
5857 | YI | APOGEE_INT |
5858 | YK | APOGEE_INT |
5859 | YP | APOGEE_INT |
5860 | YS | APOGEE_INT |
5861 | YT | APOGEE_INT |
5862 | CURBMASTER AHU | APOGEE_INT |
5863 | CURMASTER YCU | APOGEE_INT |
5864 | YG | APOGEE_INT |
5910 | SYSTEM | APOGEE_INT |
5919 | Diagnostic | APOGEE_INT |
5920 | SINGLE ROOM | APOGEE_INT |
6000 | Smart 1 Pressure Independent Cooling Only | APOGEE_INT |
6001 | Smart 1 Pressure Independent Fan Powered | APOGEE_INT |
6002 | Smart 1 Pressure Independent with Reheat | APOGEE_INT |
6003 | Smart 1 Pressure Independent Dual Duct | APOGEE_INT |
6010 | Smart 1 Pressure Dependent Cooling Only | APOGEE_INT |
6011 | Smart 1 Pressure Dependent Fan Powered | APOGEE_INT |
6012 | Smart 1 Pressure Dependent with Reheat | APOGEE_INT |
6013 | Smart 1 Pressure Dependent Dual Duct | APOGEE_INT |
6014 | Smart 1 Pressure Dependent Fan Powered | APOGEE_INT |
6020 | Smart 1 Water Source Heat Pump | APOGEE_INT |
6021 | Smart 1 Interior Zone Air to Air Heat Pump | APOGEE_INT |
6022 | Smart 1 Exterior Zone Air to Air Heat Pump | APOGEE_INT |
6030 | Smart 1 2–pipe Changeover Fan Coil Units | APOGEE_INT |
6032 | Smart 1 2–pipe Cooling only Fan Coil Units with Modulating Valves and Outside Air Damper | APOGEE_INT |
6033 | Smart 1 4–pipe Fan Coil Unit with Modulating Valves and Outside Air Damper | APOGEE_INT |
6040 | SMKI Interface | APOGEE_INT |
6050 | Smart II VAV Generic | APOGEE_INT |
6051 | Smart II VAV Cooling Only Box | APOGEE_INT |
6052 | Smart II VAV Dual Duct Box | APOGEE_INT |
6053 | Smart II VAV Series Fan Powered VAV Box with Modulating Heat Valve | APOGEE_INT |
6054 | Smart II VAV Parallel Fan Powered VAV Box with Modulating Heating Valve | APOGEE_INT |
6055 | Smart II VAV Box with Modulating Heating Valve | APOGEE_INT |
6056 | Smart II VAV Box with Digital Heating Valve | APOGEE_INT |
6057 | Smart II VAV Series Fan Powered VAV Box with Digital Heat | APOGEE_INT |
6058 | Smart II VAV Parallel Fan Powered VAV Box with Digital Heat | APOGEE_INT |
6060 | SMVU VAV Box Generic | APOGEE_INT |
6061 | SMVU VAV Cooling Only Box | APOGEE_INT |
6062 | SMVU VAV Series Fan Powered VAV Box with Modulating Heating Valve | APOGEE_INT |
6063 | SMVU VAV Parallel Fan Powered VAV Box with Modulating Heating Valve | APOGEE_INT |
6064 | SMVU VAV Box with Modulating Heating Valve | APOGEE_INT |
6065 | SMVU VAV Box with Digital Heating Valve | APOGEE_INT |
6066 | SMVU VAV Series Fan Powered VAV Box with Digital Heat | APOGEE_INT |
6067 | SMVU VAV Parallel Fan Powered VAV Box with Digital Heat | APOGEE_INT |
6070 | Smart II Heatpump Generic | APOGEE_INT |
6071 | Smart II Heatpump Single Air Cooled | APOGEE_INT |
6072 | Smart II Heatpump Single Water Cooled | APOGEE_INT |
6073 | Smart II Heatpump Multi–stage Air Cooled | APOGEE_INT |
6074 | Smart II Heatpump Multi–stage Water Cooled | APOGEE_INT |
6080 | Smart II Fan Coil Unit Generic | APOGEE_INT |
6081 | Smart II Fan Coil Unit Cooling or Heating | APOGEE_INT |
6082 | Smart II Fan Coil Unit with Modulating Cooling | APOGEE_INT |
6083 | Smart II Fan Coil Unit with Changeover Input | APOGEE_INT |
6084 | Smart II Fan Coil Unit with Changeover Relay | APOGEE_INT |
6085 | Smart II Fan Coil Unit with Digital Cooling | APOGEE_INT |
6090 | Smart II Multiplexer Generic | APOGEE_INT |
6095 | Smart II DDC Controller | APOGEE_INT |
6511 | BACnet PTEC Unit Conditioner Heating and Cooling with Multi-Speed Fan, On/Off Switch and Occupancy Sensor | APOGEE_PTEC |
6520 | VAV Cooling Only | APOGEE_PTEC |
6521 | VAV Cooling or Heating | APOGEE_PTEC |
6522 | VAV with Electric Reheat | APOGEE_PTEC |
6523 | VAV with Hot Water Reheat | APOGEE_PTEC |
6524 | VAV Series Fan Powered with Electric Reheat | APOGEE_PTEC |
6525 | VAV Series Fan Powered with Hot Water Reheat | APOGEE_PTEC |
6526 | VAV Parallel Fan Powered with Electric Reheat | APOGEE_PTEC |
6527 | VAV Parallel Fan Powered with Hot Water Reheat | APOGEE_PTEC |
6540 | VAV Pressure Depend Cooling or Heating | APOGEE_PTEC |
6541 | VAV Pressure Depend with 1 or 2 Valve Hot water Reheat | APOGEE_PTEC |
6550 | Fan Coil Unit 2-pipe Cooling/Heating with optional Heating Valve | APOGEE_PTEC |
6551 | Fan Coil Unit Cooling and Heating | APOGEE_PTEC |
6552 | Fan Coil Unit 2-stage Cooling and Electric Reheat | APOGEE_PTEC |
6553 | Fan Coil Unit 2-stage Cooling and HW Reheat | APOGEE_PTEC |
6554 | Fan Coil Unit Cooling and Electric Heat | APOGEE_PTEC |
6557 | VAV VSD Series Fan and 3-stage Electric Heat | APOGEE_PTEC |
6560 | Constant Volume Cooling Only | APOGEE_PTEC |
6562 | Constant Volume with Elect. Reheat | APOGEE_PTEC |
6563 | Constant Volume with Hot Water Reheat | APOGEE_PTEC |
6565 | BACnet PTEC Dual Duct 2 AVS | APOGEE_PTEC |
6566 | BACnet PTEC Dual Duct 2 AVS | APOGEE_PTEC |
6567 | DD VAV 2 Inlet Sensors with optional Reheat | APOGEE_PTEC |
6568 | BACnet PTEC Dual Duct 2 AVS | APOGEE_PTEC |
6569 | BACnet PTEC Dual Duct 2 AVS | APOGEE_PTEC |
6573 | BCNT HP Multi–Compressor Mixed Air Reverse Valve Control | APOGEE_PTEC |
6574 | BCNT HP HtgClg with Mixed Air and Internal Reverse Valve | APOGEE_PTEC |
6575 | BCNT UV Heating CW Cooling ASHRAE Cycle I, II | APOGEE_PTEC |
6576 | BCNT UV Heating CW Cooling ASHRAE Cycle III | APOGEE_PTEC |
6577 | BCNT UV Heating DX Cooling ASHRAE Cycle I, II | APOGEE_PTEC |
6578 | BCNT UV Heating DX Cooling ASHRAE Cycle III | APOGEE_PTEC |
6579 | BCNT UV Heating Cooling NESBITT Cycle W | APOGEE_PTEC |
6587 | VAV Terminal Box Controller - Slave Mode | APOGEE_PTEC |
6590 | BACnet Heat Pump - Slave Mode | APOGEE_PTEC |
6591 | Fan Coil Unit Conditioner - Slave Mode | APOGEE_PTEC |
6593 | DD 2 AVS - Slave Mode | APOGEE_PTEC |
6595 | BACnet Unit Vent - Slave Mode | APOGEE_PTEC |
6596 | TEC with Expanded Point I/O | APOGEE_PTEC |
6599 | VAV VSD Series Fan - Slave Mode | APOGEE_PTEC |
6600 | VAV Cooling Only | APOGEE_PTEC |
6601 | VAV Cooling or Heating | APOGEE_PTEC |
6602 | VAV with Electric Reheat | APOGEE_PTEC |
6603 | VAV with Hot Water Reheat | APOGEE_PTEC |
6604 | VAV Series Fan Powered with Electric Reheat | APOGEE_PTEC |
6605 | VAV Series Fan Powered with Hot Water Reheat | APOGEE_PTEC |
6606 | VAV Parallel Fan Powered with Electric Reheat | APOGEE_PTEC |
6607 | VAV Parallel Fan Powered with Hot Water Reheat | APOGEE_PTEC |
6608 | BCNT VAV DCV (CO2) Chill Beam | APOGEE_PTEC |
6611 | FanCoil Heat and Cool Multi–Speed Fan OCC Sensor | APOGEE_PTEC |
6620 | VAV Cooling Only | APOGEE_PTEC |
6621 | VAV Cooling or Heating | APOGEE_PTEC |
6622 | VAV with Electric Reheat | APOGEE_PTEC |
6623 | VAV with Hot Water Reheat | APOGEE_PTEC |
6624 | VAV Series Fan Powered with Electric Reheat | APOGEE_PTEC |
6625 | VAV Series Fan Powered with Hot Water Reheat | APOGEE_PTEC |
6626 | VAV Parallel Fan Powered with Electric Reheat | APOGEE_PTEC |
6627 | VAV Parallel Fan Powered with Hot Water Reheat | APOGEE_PTEC |
6630 | VAV Cooling Only | APOGEE_ATEC? |
6631 | VAV Cooling or Heating | APOGEE_ATEC |
6632 | VAV with Electric Reheat | APOGEE_ATEC |
6633 | VAV with Hot Water Reheat | APOGEE_ATEC |
6634 | VAV Series Fan Powered with Electric Reheat | APOGEE_ATEC |
6635 | VAV Series Fan Powered with Hot Water Reheat | APOGEE_ATEC |
6636 | VAV Parallel Fan Powered with Electric Reheat | APOGEE_ATEC |
6637 | VAV Parallel Fan Powered with Hot Water Reheat | APOGEE_ATEC |
6640 | VAV Pressure Dependent Cooling or Heating | APOGEE_PTEC |
6641 | VAV Pressure Dependent with 1 or 2 Valve Hot Water Reheat | APOGEE_PTEC |
6642 | VAV Pressure Dependent Cooling or Heating | APOGEE_PTEC |
6643 | VAV Pressure Dependent with 1 or 2 Valve Hot Water Reheat | APOGEE_PTEC |
6644 | Fan Coil Unit 2-pipe Cool/Heat with optional Heating Valve | APOGEE_PTEC |
6645 | Fan Coil Unit Cooling and Heating | APOGEE_PTEC |
6646 | Fan Coil Unit 2-stage Cooling and Electric Reheat | APOGEE_PTEC |
6647 | Fan Coil Unit 2-stage Cooling and Hot Water Reheat | APOGEE_PTEC |
6648 | Fan Coil Unit Cooling and Electric Heat | APOGEE_PTEC |
6650 | Fan Coil Unit 2-pipe Cool/Heat with optional Heating Valve | APOGEE_PTEC |
6651 | Fan Coil Unit Cooling and Heating | APOGEE_PTEC |
6652 | Fan Coil Unit 2-stage Cooling and Electric Reheat | APOGEE_PTEC |
6653 | Fan Coil Unit 2-stage Cooling and Hot Water Reheat | APOGEE_PTEC |
6654 | Fan Coil Unit Cooling and Electric Heat | APOGEE_PTEC |
6657 | VAV with 0-10V Series Fan and 3-stage Electric Reheat | APOGEE_PTEC |
6658 | BCNT VAV DCV (CO2) and Chilled Beam | APOGEE_PTEC |
6659 | VAV with DCV (CO2) and Chilled Beam | APOGEE_PTEC |
6660 | Constant Volume Cooling Only | APOGEE_PTEC |
6662 | Constant Volume with Electric Reheat | APOGEE_PTEC |
6663 | Constant Volume with Hot Water Reheat | APOGEE_PTEC |
6665 | Dual Duct Two Inlet Sensors with Optional Reheat | APOGEE_PTEC |
6666 | Dual Duct One Inlet One Outlet with Optional Reheat | APOGEE_PTEC |
6667 | Dual Duct VAV - Two Inlet with Optional Reheat | APOGEE_PTEC |
6668 | Dual Duct VAV-One Inlet and One Outlet with Reheat | APOGEE_PTEC |
6669 | Dual Duct VAV with Changeover | APOGEE_PTEC |
6673 | Heat Pump Multi-Comp with Mixed Air and Reversing Valve | APOGEE_PTEC |
6674 | Heat Pump Multi-Comp Heat and Cool with Mixed Air | APOGEE_PTEC |
6675 | Unit Vent 0-10V Heating/Cooling Cycles I | APOGEE_PTEC |
6676 | Unit Vent 0-10V Heating/Cooling Cycle III | APOGEE_PTEC |
6677 | Unit Vent 0-10V Heating/DX Cooling Cycles I | APOGEE_PTEC |
6678 | Unit Vent 0-10V Heating/DX Cooling Cycle III | APOGEE_PTEC |
6679 | Unit Vent 0-10V Heating/Cooling or DX Cycle W | APOGEE_PTEC |
6680 | VAV with CO2 Monitor and AOV or Floating Heat | APOGEE_PTEC |
6681 | VAV with CO2 Monitor Series Fan and AOV or Float Heat | APOGEE_PTEC |
6682 | VAV with CO2 Monitor Parallel Fan and AOV or Float Heat | APOGEE_PTEC |
6684 | VAV Terminal Box Controller – Slave Mode | APOGEE_PTEC |
6687 | VAV Terminal Box Controller - Slave Mode | APOGEE_PTEC |
6688 | VAV Terminal Box Controller - Slave Mode | APOGEE_PTEC |
6689 | Fan Coil Unit Conditioner - Slave Mode | APOGEE_PTEC |
6690 | Heat Pump - Slave Mode | APOGEE_PTEC |
6691 | Fan Coil Unit Conditioner - Slave Mode | APOGEE_PTEC |
6692 | VAV with CO2 - Slave Mode | APOGEE_PTEC |
6693 | Dual Duct - Slave Mode | APOGEE_PTEC |
6694 | Constant Volume - Slave Mode | APOGEE_PTEC |
6695 | Unit Vent 0-10v - Slave Mode | APOGEE_PTEC |
6696 | TEC with Expanded Point I/O | APOGEE_PTEC |
6697 | FanCoil – Slave Mode | APOGEE_PTEC |
6698 | VAV with CO2 Monitor – Slave Mode | APOGEE_PTEC |
6699 | VAV – Slave Mode | APOGEE_PTEC |
6700 | Fume Hood Controller – Slave Mode | APOGEE_LABS |
6720 | LRC VAV Rom Pressure with Hot Water Relative Humidity and Two Venturi Valves | APOGEE_LABS |
6721 | VAV Room Pressure with Hot Water Reheat — One Exhaust | APOGEE_PTEC |
6722 | LCM-OAVS Venturi Slow RTS | APOGEE_LABS |
6723 | LCM-OAVS Damper Slow RTS | APOGEE_LABS |
6724 | LCM-OAVS Damper/Venturi Slow RTS | APOGEE_LABS |
6726 | LRC VAV with Hot Water Relative Humidity, BTU Compensation and Two Venturi Valves | APOGEE_LABS |
6727 | VAV Room Pressure with BTU Comp Hot Water Relative Humidity and Fast Actuation | APOGEE_PTEC |
6728 | LCM-OAVS Venturi Slow BTU | APOGEE_LABS |
6729 | LCM-OAVS Damper Slow BTU | APOGEE_LABS |
6730 | LCM-OAVS Damper/Venturi Slow BTU | APOGEE_LABS |
6731 | Pressurization Control by Differential Flow Reset | APOGEE_CUSTOM |
6736 | RPC Electronic VAV with Hot Water Reheat and Humidity Control | APOGEE_LABS |
6738 | RPC Electronic CAV with Hot Water Reheat and Humidity Control | APOGEE_LABS |
6740 | Fume Hood Controller - 2–position | APOGEE_LABS |
6741 | Fume Hood Controller – VAV Damper | APOGEE_LABS |
6742 | Fume Hood Controller - VAV Venturi | APOGEE_LABS |
6750 | LRC VAV Rom Pressure with Hot Water Relative Humidity and Two Venturi Valves NEW | APOGEE_LABS |
6751 | VAV Room Pressure with Hot Water Reheat — One Exhaust NEW VAV Room Pressurization with Hot Water Reheat - One Exhaust, One Supply | APOGEE_LABS |
6752 | LCM-OAVS Venturi Slow RTS NEW | APOGEE_LABS |
6753 | LCM-OAVS Damper Slow RTS NEW | APOGEE_LABS |
6754 | LCM-OAVS Damper/Venturi Slow RTS NEW | APOGEE_LABS |
6756 | LRC VAV with Hot Water Relative Humidity, BTU Compensation and Two Venturi Valves NEW | APOGEE_LABS |
6757 | VAV Room Pressure with BTU Comp Hot Water Relative Humidity and Fast Actuation NEW | APOGEE_LABS |
6758 | LCM-OAVS Venturi Slow BTU NEW | APOGEE_LABS |
6759 | LCM-OAVS Damper Slow BTU NEW | APOGEE_LABS |
6760 | LCM-OAVS Damper/Venturi Slow BTU NEW | APOGEE_LABS |
6761 | Pressurization Control by Differential Flow Reset NEW | APOGEE_LABS |
6763 | Pressurized Room Controller (PRC) | 0APOGEE_LABS |
6765 | Pressurized Room Controller (PRC) – Slave Mode | APOGEE_LABS |
6773 | Pressurized Room Controller (PRC) NEW | APOGEE_LABS |
6775 | Pressurized Room Controller (PRC) - Slave Mode NEW | APOGEE_LABS |
6792 | Slave Mode NEW | APOGEE_LABS |
8020 | VAV Cooling | APOGEE_LON |
8022 | VAV Electric Reheat | APOGEE_LON |
8023 | VAV Hot Water | APOGEE_LON |
8024 | VAV Electric Reheat Series Fan | APOGEE_LON |
8025 | VAV Hot Water Reheat Series Fan | APOGEE_LON |
8026 | VAV Electric Reheat Parallel Fan | APOGEE_LON |
8027 | VAV Hot Water Reheat Parallel Fan | APOGEE_LON |
8032 | CV Electric Reheat | APOGEE_LON |
8033 | CV Hot Water Reheat | APOGEE_LON |
8050 | FC CW 2–pipe Hot Water Heat | APOGEE_LON |
8051 | FC CW 4–pipe | APOGEE_LON |
8052 | FC DX Electric Heat | APOGEE_LON |
8053 | FC DX Hot Water Heat | APOGEE_LON |
8054 | FC CW 2–pipe Electric Heat | APOGEE_LON |
8071 | HP REV Valve Electric Heat | APOGEE_LON |
8072 | HP Electric Heat | APOGEE_LON |
8073 | HP 2-stage REV Valve Electric Heat | APOGEE_LON |
8074 | HP 2-stage Electric Heat | APOGEE_LON |
8081 | UV CW 4-pipe | APOGEE_LON |
8084 | UV DX Hot Water Reheat | APOGEE_LON |
8086 | UV DX Electric Reheat | APOGEE_LON |
8088 | UV CW 2-pipe | APOGEE_LON |
8089 | UV FACE BYPASS 2-pipe, 4-pipe | APOGEE_LON |
8101 | VAV Electric Reheat Variable Speed Fan | APOGEE_CUSTOM |
8102 | VAV HW Reheat Variable Speed Fan | APOGEE_CUSTOM |
14020 | VAV Cooling Only | APOGEE_DXR |
14022 | VAV with 2-stage Electric Heat | APOGEE_DXR |
14023 | VAV Hot Water | APOGEE_DXR |
14123 | VAV Hot Water with Supply Temperature Control | APOGEE_DXR |
14024 | VAV Series Fan Powered Box with 2-stage Electric Heat | APOGEE_DXR |
14025 | VAV Series Fan Powered Box with Hot Water | APOGEE_DXR |
14125 | VAV Series Fan Powered Box with Hot Water and Supply Temperature Control | APOGEE_DXR |
14026 | VAV Parallel Fan Powered Box with 2-stage Electric Heat | APOGEE_DXR |
14027 | VAV Parallel Fan Powered Box with Hot Water | APOGEE_DXR |
14127 | VAV Parallel Fan Powered Box with Hot Water and Supply Temperature Control | APOGEE_DXR |
14050 | Fan Coil 2-pipe Heating/Cooling and Hot Water Coil | APOGEE_DXR |
14051 | Fan Coil 4-pipe with Chilled Water and Hot Water | APOGEE_DXR |
14052 | Fan Coil with 2-stage DX Cool and 2-stage Electric Heat | APOGEE_DXR |
14054 | Fan Coil with Chilled Water and 2-stage Electric Heat | APOGEE_DXR |
14058 | Chilled Beam Passive Heating and Cooling and Hot Water Radiator | APOGEE_DXR |
14064 | Dual Duct Variable Volume with Dedicated Ventilation Duct, Two Inlet Sensors, DCV and Hot Water Heat with Supply Temp Control NEW | APOGEE_DXR |
14069 | Dual Duct Variable Volume with Two Inlet Sensors and Hot Water Radiator New | APOGEE_DXR |
14081 | Fan Coil Unit Vent with Chilled Water and Hot Water and OA Damper | APOGEE_DXR |
14083 | Fan Coil Unit Vent with Chilled Water and 2-stage Electric Heat and OA Damper | APOGEE_DXR |
14070 | HP Var Spd with RV, Vari-Spd Fan, 2-Stg Elec Heat and 1-Sg Elec Rad and OAD | APOGEE_DXR |
14071 | HP Multi-Stg with RV Multi-Spd Fan 2-Stg Elec Heat and HW Rad and OAD | APOGEE_DXR |
14072 | HP Multi-Stg Gnd Src with Int RV and HG Rht Vari-Spd Fan 1-Stg Elec Heat HW Rad and OAD | APOGEE_DXR |
14084 | Fan Coil Unit Vent with 2-stage DX Cool and HW and OA Damper | APOGEE_DXR |
14158 | Chilled Beam Active Heating and Cooling with VAV and Hot Water Radiator | APOGEE_DXR |
14169 | Dual Duct Variable Volume with Two Inlet Sensors, DCV and Hot Water Radiator NEW | APOGEE_DXR |
14171 | HP Multi-Stg with RV and H Gas Rht Multi-Spd Fan 1-Stg Elec Heat and HW Rad and OAD | APOGEE_DXR |
14184 | Fan Coil Unit Vent with 2-stage DX Cool and 2-stage Electric Heat and OA Damper | APOGEE_DXR |
14258 | Chilled Beam Active Heating and Cooling with VAV and Electric 1-stage Radiator | APOGEE_DXR |
14269 | Dual Duct Variable Volume with Two Inlet Sensors, Chilled Ceiling and Hot Water Radiator NEW | APOGEE_DXR |
14270 | HP 1-Stg with RV 1-Spd Fan 1-Stg Elec Heat and HW Rad and OAD | APOGEE_DXR |
14358 | Chilled Beam Passive 2-pipe Heating/Cooling and Electric 1-stage Radiator | APOGEE_DXR |
14369 | Dual Duct Variable Volume with Two Inlet Sensors, Hot Water Heat and 1-Stage Electric Radiator | APOGEE_DXR |
14458 | Chilled Beam Passive 2-pipe Heating/Cooling and Electric 1-Stage Radiator NEW | APOGEE_DXR |
14550 | Fan Coil 2-pipe Heating/Cooling and Hot Water Coil | APOGEE_DXR |
14551 | Fan Coil 4-pipe with Chilled Water and Hot Water | APOGEE_DXR |
14552 | Fan Coil with 2-stage DX Cool and 2-stage Electric Heat | APOGEE_DXR |
14554 | Fan Coil with Chilled Water and 2-stage Electric Heat | APOGEE_DXR |
14581 | Fan Coil Unit Vent with Chilled Water and Hot Water and OA Damper | APOGEE_DXR |
14583 | Fan Coil Unit Vent with Chilled Water and 2-stage Electric Heat and OA Damper | APOGEE_DXR |
14584 | Fan Coil Unit Vent with 2-stage DX Cool and HW and OA Damper | APOGEE_DXR |
14670 | HP 1-Stg with RV 1-Spd Fan 1-Stg Elec Heat and HW Rad and OAD NEW | APOGEE_DXR |
14684 | Fan Coil Unit Vent with 2-stage DX Cool and 2-stage Electric Heat and OA Damper | APOGEE_DXR |
14720 | ADXR VAV Cooling Only NEW | APOGEE_DXR |
14722 | ADXR VAV with 2-Stage Electric Heat NEW | APOGEE_DXR |
14723 | ADXR VAV Hot Water NEW | APOGEE_DXR |
14724 | ADXR VAV Series Fan Powered Box with 2-Stage Electric Heat NEW | APOGEE_DXR |
14725 | ADXR VAV Series Fan Powered Box with Hot Water NEW | APOGEE_DXR |
14726 | ADXR VAV Parallel Fan Powered Box with 2-Stage Electric Heat NEW | APOGEE_DXR |
14727 | ADXR VAV Parallel Fan Powered Box with Hot Water NEW | APOGEE_DXR |
14820 | ADXR VAV Cooling Only – UFAD NEW | APOGEE_DXR |
14823 | ADXR VAV Hot Water with Supply Temp Control NEW | APOGEE_DXR |
14825 | ADXR VAV Series Fan Powered Box with Hot Water and Supply Temp Control NEW | APOGEE_DXR |
14827 | ADXR VAV Parallel Fan Powered Box with Hot Water and Supply Temp Control NEW | APOGEE_DXR |
14828 | ADXR VAV Parallel Fan Powered Box with Hot Water and Supply Temp Control – UFAD NEW | APOGEE_DXR |
14900 | RDY2000BN BACnet Thermostat Conventional | APOGEE_BTEC |
14901 | RDY2000BN BACnet Thermostat Heat Pump | APOGEE_BTEC |
16741 | Fume Hood Vertical Sash Configuration with Modulating Damper | APOGEE_DXR |
16742 | Fume Hood Vertical Sash Configuration with Modulating Venturi | APOGEE_DXR |
16750 | Lab Room VAV Pressurization with Fast-Action Venturi Air Valves and HW Reheat | APOGEE_DXR |
16751 | Lab Room VAV Pressurization with Fast-Action Dampers and HW Reheat | APOGEE_DXR |
16756 | Lab Room VAV Pressurization with Fast-Action Venturi Air Valves and HW Reheat – Thermal Power Control | APOGEE_DXR |
16773 | Lab Room VAV Pressurization with Slow Floating Dampers, HW Reheat, Supply Temp | APOGEE_DXR |
16850 | Lab Room VAV Pressurization with Fast-Action Venturi Air Valves and HW Reheat | APOGEE_DXR |
16851 | Lab Room VAV Pressurization with Fast-Action Dampers and HW Reheat | APOGEE_DXR |
16856 | Lab Room VAV Pressurization with Fast-Action Venturi Air Valves and HW Reheat - Thermal Power Control | APOGEE_DXR |
65535 | Undefined or failed BACnet FLN Device | APOGEE_MISC |
- System Manager is in Engineering mode.
- In System Browser, select Management View > System Settings > Libraries.
- Click the Library Configurator tab.
- Click the Import button.
- The Import Libraries dialog box displays.
- Select the [GMSProject] > Libraries > Exports folder.
- From the list of libraries, select only the FLN libraries you need for your project—those that correspond to your FLN applications.
- Click Open.
- When asked if you want to import the folder structures for the various libraries, click Yes for individual libraries, or Yes to all for all the libraries you selected.
- The folder structure is added to the Libraries > BA (HQ) > Room equipment folder.